Connection to the PROFIBUS DP
 
Connector
The following connectors can be used for the connection to the PROFIBUS DP.
Description
Part No.
PROFIBUS connector with termination (yellow)
490 NAD 911 03
PROFIBUS connector node (gray)
490 NAD 911 04
PROFIBUS connector node with diagnostics interface (gray)
490 NAD 911 05
Communications Adapter Interface Assignment
Communications adapter pin assignment (sockets)
Interface assignment
Terminal
Signal
Meaning
3
RxD/TXD-P
Incoming data (RxD) positive,
Outgoing data (TxD) positive
5
DGND
Reference potential for terminations (supplied by the I/O module)
6
VP
Supply voltage for terminations (+5 V supplied by the I/O module)
8
RxD/TXD-N
Incoming data (RxD-N) negated,
Outgoing data (TxD-N) negated
1, 2, 4, 7, 9
Pin not connected
Connector housing
Cable shield connection (internally connected)