Performance Characteristics

The alarm relay terminal block on the M580 safety power supplies present the following performance characteristics:

Characteristics

Rated switching Voltage / Current

24 Vdc 2A (Restive load)

240 Vac 2A (cos φ =1) point

Minimum switching load

5 Vdc 1 mA

Maximum switching voltage

62.4 Vdc

264 Vac

Contact type

Normally open

Contact time

  • OFF → ON

10 ms or Less

  • ON → OFF

12 ms or Less

Built-in protection

Against overload / short-circuits: none, a fast-blow fuse must be fitted.

Against inductive overvoltage in AC: none, an RC circuit or a MOV (ZNO) suppressor (appropriate to the voltage) must be fitted in parallel to the terminals of each pre-actuator.

Against inductive overvoltage in DC: none, a discharge diode must be fitted to the terminals of each pre-actuator.

Dielectric strength

Contact vs ground: 2000 Vrms 50Hz 1min.(Altitude 0...2000 m)

Insulation resistance

10 MΩ or more under 500 Vdc