BMXCPS4002S Safety Power Supply
The BMXCPS4002S safety power supply provides the following performance characteristics:
Input characteristics |
||
---|---|---|
Nominal Voltage |
100...240Vrms |
|
Voltage range |
85...132Vrms 170...264Vrms |
|
Frequency range |
47...63Hz |
|
Masked input power outages |
Max 10ms @100Vrms-15% & @200Vrms-15% |
|
Typical Input apparent Power |
130VA |
|
Typical input current |
1.1Arms @115Vrms 0.55Arms @230Vrms |
|
Inrush Current @25° @ 1st start-up |
Peak |
30Arms @115Vrms 60Arms @230Vrms |
I2t (for rating external fuse) |
1A2s @115Vrms 4A2s @230Vrms |
|
It (for rating external breaker) |
0.1As @115Vrms 0.15As @230Vrms |
|
Integrated Protection |
Internal non-accessible fuse located on L input |
Output characteristics |
||
---|---|---|
MAX 3V3_BAC output current |
5.5A (18.2W) |
|
MAX 24V_BAC output current |
1.67A (40W) |
|
MAX Total output power |
40W |
|
Detection |
Overload |
Yes - Disjunction |
Short-circuit |
Yes - Disjunction |
|
Overvoltage |
Yes - Disjunction |
Other characteristics |
||
---|---|---|
Dielectric |
Primary/All Secondaries |
SELV / PELV |
Strength |
Primary/Ground |
SELV / PELV |
Insulation Resistance |
Primary/All Secondaries |
100MΩ |
Primary/Ground |
100MΩ |
BMXCPS4022S Safety Power Supply
Input characteristics |
||
---|---|---|
Nominal Voltage Type |
24...48 Vdc |
|
Input Voltage Range |
18...62.4 Vdc |
|
Efficiency |
max losses ≤7W (efficiency ≥84.8%) at maximum continuous load, over entire input voltage range, and temperature range |
|
Nominal Input Current |
1.9 A @ 24 Vdc |
|
1.0 A @ 48 Vdc |
||
Inrush current at first start-up @25°C |
Peak current |
≤60 A @ 24 Vdc |
≤60 A @ 48 Vdc |
||
I2t (for rating external fuse) |
≤ X A2s @ 24 Vdc |
|
≤ X A2s @ 48 Vdc |
||
It (for rating external breaker) |
≤ X As @ 24 Vdc |
|
≤ X As @ 48 Vdc |
||
Masked input power outages |
Any input power outage lasting at max: |
|
|
||
|
||
Must not induce any change in the output characteristics. Period between interruptions 1 sec. |
||
Input Protection |
|
|
|
Output characteristics: |
|
---|---|
Output Nominal Voltage |
24.35 V |
Output Steady-State Voltage Range |
23.3...24.7 V over the entire input voltage range, over the full output load range, and over the full temperature range. |
Output Ripple and Noise |
240 mV peak to peak (measured with a bandwidth ≥100 MHz, on the module connector pins. |
Continuous Output Current Range |
|
|
|
Transient Output Current Capability |
1.9 A maximum during 500 ms, period minimum 20 sec. |
Output impedance versus frequency |
180 mΩ |
Output Voltage Response to transient load on 24V_BAC |
For the following output load transient on 24V_BAC: |
|
|
|
|
|
|
|
|
Protection against output overload/short-circuit |
|
|
|
|
|
Protection against overvoltage |
Disjunction of the power supply for a rise of the output reaching 30.0 Vdc ±.8 V. |
External Capacitive Load Capability |
All the above characteristics must be fulfilled with the following external capacitive load value. This feature must be considered notably for slope-up, regulation loop stability and overload detection/protection. |
11500 μF capacitive value. |
BMXCPS3522S Safety Power Supply
Input characteristics: |
||
---|---|---|
Nominal Voltage Type |
125 Vdc |
|
Input Voltage Range |
100...150 Vdc |
|
Efficiency |
max losses ≤7W (efficiency ≥84.8%) @max continuous load, over entire input voltage range & temperature range |
|
Nominal Input Current |
0.6 A @ 125 Vdc |
|
Inrush current at first start-up @25°C |
Peak current |
≤60 A @ 125 Vdc |
I2t (for rating external fuse) |
≤ X A2s @ 125 Vdc |
|
It (for rating external breaker) |
≤ X As @ 4 Vdc |
|
Masked input power outages |
Any input power outage lasting at max : |
|
|
||
|
||
Must not induce any change in the output characteristics. Period between interruptions 1 sec. |
||
Input Protection |
|
|
|
BMXCPS3522 /S High Power |
|
---|---|
Output Nominal Voltage |
24.35 V |
Output Steady-State Voltage Range |
23.3...24.7 V over the entire input voltage range, over the full output load range and over the full temperature range. |
Output Ripple and Noise |
240 mV peak to peak (measured with a bandwidth ≥100 MHz, on the module connector pins. |
Continuous Output Current Range |
|
|
|
Transient Output Current Capability |
1.9 A maximum during 500ms, period minimum 20 sec. |
Output impedance versus frequency |
180 mΩ |
Output Voltage Response to transient load on 24V_BAC |
For the following output load transient on 24V_BAC: |
|
|
|
|
|
|
|
|
Protection against output overload/short-circuit |
|
|
|
|
|
Protection against overvoltage |
Disjunction of the power supply for a rise of the output reaching 30.0 Vdc ±.8 V. |
External Capacitive Load Capability |
All the above characteristics must be fulfilled with the following external capacitive load value. This feature must be considered notably for slope-up, regulation loop stability and overload detection/protection. |
11500 μF capacitive value. |