Detected Error Codes
The following detected error codes and sub-codes apply to the T_CIP_SAFETY_STATUS data type, and are included in the Status_IN and Status_OUT parameters of the CIP Safety device DDDT.
Detected Error Codes
Detected Error Code |
Meaning |
---|---|
0001 |
Open connection: no response. |
0002 |
Open connection: detected error response from device. |
0003 |
Open connection: invalid response from device. |
0004 |
Server (consumer) is non-operational. |
0005 |
Client (producer) is non-operational. |
Detected Error Sub-Codes
Detected error sub-codes for Open connections:
Detected Error Sub-Code (hex) |
Meaning |
---|---|
0100 |
Connection in use or duplicate Forward_Open. |
0103 |
Transport class and trigger combination not supported. |
0105 |
Configuration is already owned by another originator. |
0106 |
Output is already owned by another originator. |
0107 |
Target connection not found (Forward_Close). |
0108 |
Invalid network connection parameter. |
0109 |
Invalid connection size. |
0110 |
Device not configured. |
0111 |
O->T RPI, T->O RPI, or Time Correction RPI not supported. |
0113 |
All Safety validator Instances are being used. |
0114 |
Device_Vendor_ID or Device_Product_Code specified in the electronic key does not match. |
0115 |
Device_Type specified in the electronic key does not match. |
0116 |
Major_Revision or Minor_Revision specified in the electronic key does not match. |
0117 |
Invalid produced or consumed application path. |
0118 |
Invalid or inconsistent configuration application path. |
011A |
Target object out of connections. |
011B |
RPI is smaller than the production inhibit time. |
011C |
Transport class not supported. |
011D |
Production trigger not supported. |
011E |
Direction not supported. |
0123 |
Invalid Originator to Target Network Connection Type. |
0124 |
Invalid Target to Originator Network Connection Type. |
0126 |
Invalid Configuration Size. |
0127 |
Invalid Originator to Target Size. |
0128 |
Invalid Target to Originator Size. |
0129 |
Invalid Configuration Application Path. |
012A |
Invalid Consuming Application Path. |
012B |
Invalid Producing Application Path. |
012C |
Configuration Symbol does not exist. |
012D |
Consuming Symbol does not exist. |
012E |
Producing Symbol does not exist. |
012F |
Inconsistent Application Path Combination. |
0130 |
Inconsistent Consume Data Format. |
0131 |
Inconsistent Produce Data Format. |
0203 |
Connection timed out. |
0204 |
Target did not respond on unconnected request. |
0205 |
Parameter detected error in SafetyOpen request. |
0207 |
Unconnected acknowledgement without reply. |
0315 |
Invalid segment type in connection path. |
031B |
Module connection already established. |
031C |
No other extended status code applies. |
031F |
No more user configurable link consumer resources available in the producing module. |
0801 |
Ping_Interval_EIP_Multiplier or Max_Consumer_Number invalid on multicast join. |
0802 |
Invalid safety connection size. |
0803 |
Invalid safety connection format. |
0804 |
Invalid time correction connection parameters. |
0805 |
Invalid Ping_interval_EIP_Multiplier. |
0806 |
Invalid Time_Coordination_Msg_Min Multiplier. |
0807 |
Invalid Network_Time_Expectation_Mult. |
0808 |
Invalid Timeout Multiplier. |
0809 |
Invalid Max Consumer Number. |
080A |
Invalid CPCRC. |
080B |
Time Correction Connection ID invalid. |
080C |
SCID mismatch. |
080D |
TUNID not set. |
080E |
TUNID mismatch. |
080F |
Configuration operation not allowed. |
Detected error sub-codes for server or client:
Detected Error Sub-Code (hex) |
Meaning |
---|---|
271D |
Time Coordination Message was received with Ping_Response bit not set. |
2730 |
Time coordination message: Not received in allotted time. |
2732 |
Time Coordination Message Check: message with same time stamp already received from this consumer. |
2733 |
Time Coordination Message Check: parity check detected error. |
2734 |
Time Coordination Message Check: Ack_Byte_2 check detected error. |
2735 |
Time Coordination Message Check: not received within the approximatley 5 second limit. |
2736 |
Time Coordination Message Check: not received within the same ping interval or the next ping interval. |
2738 |
Time Coordination Message Check: CRC mismatch. |
2820 |
Timestamp CRC mismatch. |
2821 |
Timestamp Delta zero. |
2822 |
Timestamp Delta greater than Network Time Expectation. |
2823 |
Data age of a faulty message greater than Network Time Expectation. |
2824 |
Data age of an in other respects valid message greater than Network Time Expectation. |
2825 |
Actual Data CRC mismatch. |
2826 |
Complemented Data CRC mismatch. |
282E |
Actual data CRC mismatch (no close of the connection). |
282F |
Complemented data CRC mismatch (no close of the connection). |
2832 |
Consumer activity monitor timeout. |