Detected Error Codes

The following detected error codes and sub-codes apply to the T_CIP_SAFETY_STATUS data type, and are included in the Status_IN and Status_OUT parameters of the CIP Safety device DDDT.

Detected Error Codes

Detected Error Code

Meaning

0001

Open connection: no response.

0002

Open connection: detected error response from device.

0003

Open connection: invalid response from device.

0004

Server (consumer) is non-operational.

0005

Client (producer) is non-operational.

Detected Error Sub-Codes

NOTE: Any detected error sub-codes, other than those listed below, are intended for Schnieder Electric’s internal use. In this case, report the detected error sub-code to Schneider Electric support.

Detected error sub-codes for Open connections:

Detected Error Sub-Code (hex)

Meaning

0100

Connection in use or duplicate Forward_Open.

0103

Transport class and trigger combination not supported.

0105

Configuration is already owned by another originator.

0106

Output is already owned by another originator.

0107

Target connection not found (Forward_Close).

0108

Invalid network connection parameter.

0109

Invalid connection size.

0110

Device not configured.

0111

O->T RPI, T->O RPI, or Time Correction RPI not supported.

0113

All Safety validator Instances are being used.

0114

Device_Vendor_ID or Device_Product_Code specified in the electronic key does not match.

0115

Device_Type specified in the electronic key does not match.

0116

Major_Revision or Minor_Revision specified in the electronic key does not match.

0117

Invalid produced or consumed application path.

0118

Invalid or inconsistent configuration application path.

011A

Target object out of connections.

011B

RPI is smaller than the production inhibit time.

011C

Transport class not supported.

011D

Production trigger not supported.

011E

Direction not supported.

0123

Invalid Originator to Target Network Connection Type.

0124

Invalid Target to Originator Network Connection Type.

0126

Invalid Configuration Size.

0127

Invalid Originator to Target Size.

0128

Invalid Target to Originator Size.

0129

Invalid Configuration Application Path.

012A

Invalid Consuming Application Path.

012B

Invalid Producing Application Path.

012C

Configuration Symbol does not exist.

012D

Consuming Symbol does not exist.

012E

Producing Symbol does not exist.

012F

Inconsistent Application Path Combination.

0130

Inconsistent Consume Data Format.

0131

Inconsistent Produce Data Format.

0203

Connection timed out.

0204

Target did not respond on unconnected request.

0205

Parameter detected error in SafetyOpen request.

0207

Unconnected acknowledgement without reply.

0315

Invalid segment type in connection path.

031B

Module connection already established.

031C

No other extended status code applies.

031F

No more user configurable link consumer resources available in the producing module.

0801

Ping_Interval_EIP_Multiplier or Max_Consumer_Number invalid on multicast join.

0802

Invalid safety connection size.

0803

Invalid safety connection format.

0804

Invalid time correction connection parameters.

0805

Invalid Ping_interval_EIP_Multiplier.

0806

Invalid Time_Coordination_Msg_Min Multiplier.

0807

Invalid Network_Time_Expectation_Mult.

0808

Invalid Timeout Multiplier.

0809

Invalid Max Consumer Number.

080A

Invalid CPCRC.

080B

Time Correction Connection ID invalid.

080C

SCID mismatch.

080D

TUNID not set.

080E

TUNID mismatch.

080F

Configuration operation not allowed.

Detected error sub-codes for server or client:

Detected Error Sub-Code (hex)

Meaning

271D

Time Coordination Message was received with Ping_Response bit not set.

2730

Time coordination message: Not received in allotted time.

2732

Time Coordination Message Check: message with same time stamp already received from this consumer.

2733

Time Coordination Message Check: parity check detected error.

2734

Time Coordination Message Check: Ack_Byte_2 check detected error.

2735

Time Coordination Message Check: not received within the approximatley 5 second limit.

2736

Time Coordination Message Check: not received within the same ping interval or the next ping interval.

2738

Time Coordination Message Check: CRC mismatch.

2820

Timestamp CRC mismatch.

2821

Timestamp Delta zero.

2822

Timestamp Delta greater than Network Time Expectation.

2823

Data age of a faulty message greater than Network Time Expectation.

2824

Data age of an in other respects valid message greater than Network Time Expectation.

2825

Actual Data CRC mismatch.

2826

Complemented Data CRC mismatch.

282E

Actual data CRC mismatch (no close of the connection).

282F

Complemented data CRC mismatch (no close of the connection).

2832