M580 Hot Standby System Diagnostics
Original instructions
Introduction
The M580 Hot Standby system continuously monitors the system state, and adds to its diagnostic buffer an entry for each detected error or change of state event. You can view and handle this collection of events using the following tools:
M580 Hot Standby System Messages
Each detected system event presents:
The M580 Hot Standby system can display the following messages
ID (dec)
Message (Event Text)
Symbol (Event Type)
Possible Cause
14101
Switch from Wait to Primary
No Error
14102
Switch From Wait to Standby
Linked to Primary. No Error
14103
Switch from Standby to Primary
No remote PLC connection
No Hot Standby link and EIO link between CPUs.
14104
Switch from Standby to Primary
Remote PLC not Primary
  • Loss of power on former primary.
  • Former primary stopped.
  • Error detected on former primary.
14105
Switch from Standby to Wait
Hsby Link Error
  • Break in Hot Standby link cable
  • Transceiver inoperable in either CPU.
14106
Switch from Standby to Stop
PLC not in RUN
Standby CPU stopped.
14107
Switch from Primary to Wait
Loc RIO err and no peer RIO err
Former primary CPU lost connection to all (e)X80 EIO adapter modules; former standby (now primary) CPU maintains connection to at least one (e)X80 EIO adapter module.
14108
Switch from Primary to Wait
Swap Command
Former primary CPU received swap command.
14109
Switch from Primary to Stop
PLC not in RUN
Former primary CPU stopped (PAC in STOP or one task in HALT)
14110
Switch from Primary to Wait
PLC_B linked to Primary
14111
Peer PLC disconnection on RIO Link
RIO Link Error
Two breaks in Ethernet RIO cable have isolated the remote CPU.
14112
Peer PLC disconnection on Hsby Link
Hsby Link Error
  • Break in Hot Standby link cable
  • Transceiver inoperable in either CPU.
14113
Mismatch Error
FW mismatch
Different firmware versions in each CPU.
14114
Mismatch Error
Logic mismatch
Different application logic revisions running in each CPU.
14115
Mismatch Error
Application mismatch
Different applications running in each CPU.
14116
Degraded Hsby Data transfer
Data Layout mismatch
Online changes to data structure have been made to primary CPU, but not transferred to standby.
14117
Bad peer rotary switch config
Not in a PLC_A and PLC_B config
Rotary switch settings do not specify an A and a B PAC.
14118
Power supply error
Loss of redundancy
One of the BMXCPS4002 redundant power supply units is no longer functioning.