EtherNet/IP hexadecimal detected error codes include:
Detected Error Code (hex)
Description
800D
Timeout on the explicit message request
8012
Bad device
8015
Either:
  • Nor resources to handle the message, or
  • Internal detected error: no buffer available, no link available, impossible to send to the TCP task
8018
Either:
  • Another explicit message for this device is in progress, or
  • TCP connection or encapsulation session in progress
8030
Timeout on the Forward_Open request
Note: The following 81xx detected errors are Forward_Open response detected errors that originate at the remote target and are received via the CIP connection.
8100
Connection in use or duplicate Forward_Open
8103
Transport class and trigger combination not supported
8106
Ownership conflict
8107
Target connection not found
8108
Invalid network connection parameter
8109
Invalid connection size
8110
Target for connection not configured
8111
RPI not supported
8113
Out of connections
8114
Vendor ID or product code mismatch
8115
Product type mismatch
8116
Revision mismatch
8117
Invalid produced or consumed application path
8118
Invalid or inconsistent configuration application path
8119
Non-Listen Only connection not opened
811A
Target object out of connections
811B
RPI is smaller than the production inhibit time
8123
Connection timed out
8124
Unconnected request timed out
8125
Parameter detected error in unconnected request and service
8126
Message too large for unconnected_send service
8127
Unconnected acknowledge without reply
8131
No buffer memory available
8132
Network bandwidth not available for data
8133
No consumed connection ID filter available
8134
Not configured to send scheduled priority data
8135
Schedule signature mismatch
8136
Schedule signature validation not possible
8141
Port not available
8142
Link address not valid
8145
Invalid segment in connection path
8146
Detected error in Forward_Close service connection path
8147
Scheduling not specified
8148
Link address to self invalid
8149
Secondary resources unavailable
814A
Rack connection already established
814B
Module connection already established
814C
Miscellaneous
814D
Redundant connection mismatch
814E
No more user-configurable link consumer resources: the configured number of resources for a producing application has reached the limit
814F
No more user-configurable link consumer resources: there are no consumers configured for a producing application to use
8160
Vendor specific
8170
No target application data available
8171
No originator application data available
8173
Not configured for off-subnet multicast
81A0
Detected error in data assignment
81B0
Optional object state detected error
81C0
Optional device state detected error
Note: All 82xx detected errors are register session response detected errors.
8200
Target device does not have sufficient resources
8208
Target device does not recognize message encapsulation header
820F