Details of EFB TCP/IP Ethernet Error Codes 5mss
Original instructions
TCP/IP Ethernet Network Specific Error Codes (5mss)
NOTE: Ethernet errors are managed by the Ethernet modules or the Ethernet coprocessor except for error code 5050 (hex).
Hex. Error Code
Meaning
5001
Inconsistent response by the network
5004
Interrupted system call
5005
I/O error
5006
No such address
5009
Socket descriptor is invalid
500C
Not enough memory
500D
Authorization denied
5011
Entry exists
5016
Argument is invalid
5017
Internal table has run out of space
5020
Connection is lost
5023
This operation was blocked and the socket is non-blocking
5024
The socket is non-blocking and the connection can not be closed
5025
The socket is non-blocking and a previous connection attempt has not been finalized
5026
Socket operation performed on a non-socket
5027
The destination address is not valid
5028
Message too long
5029
Wrong type of protocol for the socket
502A
Protocol not available
502B
Protocol not supported
502C
Socket type not supported
502D
Operation not supported on a socket
502E
Protocol family not supported
502F
Address family not supported
5030
Address already in use
5031
Address not available
5032
Network is out of order
5033
Network is unreachable
5034
Network dropped connection on reset
5035
Connection aborted by the peer
5036
Connection reset by the peer
5037
An internal buffer is required but can not be assigned
5038
Socket already connected
5039
Socket not connected
503A
Cannot send after socket shutdown
503B
Too many references, cannot splice
503C
Connection timed out (see note below)
503D
Connection refused
5040
Host is out of order
5041
The destination host could not be reached from this node
5042
Directory not empty
5046
NI_INIT returned ‘-1’
5047
MTU is not valid
5048
Hardware length is not valid
5049
Route specified cannot be found
504A
Collision in Select call: these conditions have already been selected by another task
504B
Task ID is invalid
5050
No network resource
5051
Length error
5052
Addressing error
5053
Application error
5054
Client can not process the request
5055
No network resource
5056
Non-operational TCP connection
5057
Incoherent configuration
51ss
53ss
NOTE:
  • Error code 5055 (hex) can occur before an error code 503C (hex).
  • No remote device takes precedence over a timeout.
SMTP Service Error Codes (51ss)
Hexadecimal SMTP service error codes:
Hex. Error Code
Meaning
5100
Internal error
5101
SMTP component not operational
5102
Mail header not configured
5103
Invalid mail header value
5104
Cannot connect to the SMTP server
5105
Error in transmitting content of email body to the SMTP server
5106
Closing SMTP connection with the server returned an error
5107
SMTP HELO request failed
5108
SMTP MAIL request failed. SMTP server may require authentication
5109
SMTP RCPT request failed
510A
No recipient has been accepted by the SMTP server
510B
SMTP DATA request failed
510C
Send email request contains an invalid length
510D
Authentication failed
510E
A reset component request has been received while the connection was open
Modbus Client Service Error Codes (53ss)
Hexadecimal Modbus client service error codes:
Hex. Error Code
Meaning
5300
Not used (reserved for future use)
5301
The component has run out of resources
5302
The IP address provided is not appropriate. For example: 0.0.0.0, or broadcast address, or multicast address, etc.
5303
The transaction has timed-out. The remote server accepted a request and has not answered within 2 minutes.
5304
All connections are currently used
5305
Access denied
5306
Network can not be reached
5307
Host is down
5308
Network dropped connection on reset
5309
Network is down
530A
Connection refused
530B
Connection timed out
530C
Wrong MBAP header