Replacement of AS-J89X-X0X Adapters
(Original Document)
Overview
The ASP890300 is not physically compatible if installations use the following adapter models.
AS-J890-001
AS-J892-001
AS-J890-002
AS-J892-002
AS-J890-101
AS-J892-101
AS-J890-102
AS-J892-102
In these installations, you will need to:
Primary Backplane Replacement
ASP890300 modules are compatible with:
*Repair/service exchange only.
Power Considerations
If the primary backplane power requirements exceed the ASP890300 capabilities, enough I/O modules must be removed from the primary backplane to bring the current load within specified limits. In this case, an additional backplane and power supply will need to be added in the configuration unless the extra modules can be added to an existing powered backplane. For further reference, see Power Supply Capacities in Remote Drop Secondary Applications and I/O Module Current Requirements.
Secondary backplanes AS-H819-100 and AS-H827-100 support 7 and 11 I/O modules, respectively. Subtract two modules if power supplies need to be added.
Backplane Interconnection Cables
See Backplane Interconnection Diagrams for appropriate configurations.
ASCII Port Pinout Comparison
The following table shows how the ASCII port pinouts are used on the J892 and ASP890300.
Terminal
J892 (25 pin)
ASP890300 (9 pin)
1
Shield
Not Used
2
TXD
RXD
3
RXD
TXD
4
RTS
DTR
5
CTS
SGND
6
DSR
DSR
7
Ground
RTS
8
Not Used
CTS
20
DTR
N/A
Coaxial Cable Interconnection/Terminations
AS-J89X-00X Remote I/O Adapters - These have BNC type connectors which are not compatible with the F style connections on ASP890300 modules. Installers may use BNC Jack to Male "F" Connector Adapters, part number 52-0724-000. The external 75 terminator added in series with the coax drop cable must be removed as the ASP890300 is terminated internally.
AS-J890-10X Remote I/O Adapters are compatible in this respect. They have "F" type coaxial cable connectors and are terminated internally.