B875–200 Configurable A/D Input, Available Input Packs
(Original Document)
General
The module accepts up to eight input packs of any mix. Six categories are available
Refer to the following tables for the desired input range, output range, and part number required for the intended application.
NOTE: 5B type third party packs
When using third party packs, contact the manufacturer for support.
NOTE: Input packs are issued as revision level A’s, denoted by the last item of the part number, for example, (AS–5B30001A). Changes will be noted by higher revision levels.
NOTE: The usable output range for all AS–5BXX input packs is 0—+5 V when used with this module.
Low Bandwidth (4 kHz) Analog Voltage Input Packs
The following table presents the part numbers and input ranges for the available low bandwidth analog voltage input packs.
Part Number
Input Range
AS–5B30001A
0—10 mV
AS–5B30002A
0—50 mV
AS–5B30003A
0—100 mV
AS–5B30004A
-10—+10 mV
AS–5B30005A
-50—+50 mV
AS–5B30006A
-100—+100 mV
AS–5B31001A
0—1 V
AS–5B31002A
0—5 V
AS–5B31003A
0— +10 V
AS–5B31004A
-1— +1 V
AS–5B31005A
-5— +5 V
AS–5B31006A
-10— +10 V
Low Bandwidth (4 kHz) Analog Current Input Packs
The following table presents the part numbers and input ranges for the available low bandwidth analog current input packs.
Part Number
Input Range
AS–5B32001A
4—20 mA
AS–5B32002A
0—20 mA
NOTE: Each current input pack (4—20 mA) comes with a fusible resistor that must be inserted in addition to the input pack.
Low bandwidth (4k Hz) RTD Input Packs
The following table presents the part numbers, types, and input ranges for the available low bandwidth RTD input packs.
Part Number
Type
Input Range
AS–5B34P01A
100 Ω Pt
-100— +100°C (-148— +212°F)
AS–5B34P02A
100 Ω Pt
0—100°C (32—212°F)
AS–5B34P03A
100 Ω Pt
0—200°C (32—392°F)
AS–5B34P04A
100 Ω Pt
0—600°C (32—1112°F)
AS–5B34C01A
100 Ω Cu @ 0°C
0—120°C (32—248°F)
AS–5B34C02A
100 Ω Cu @ 25°C
0—120°C (32—248°F)
AS–5B34N01A
120 Ω Ni
0—300°C (32—572°F)
Wide Bandwidth (10 kHz) Strain Gauge/Load Cell Input Packs
The following table presents the part numbers and input ranges for the available wide bandwidth strain gauge/load cell input packs.
Part Number
Input Range
AS–5B38002A
3 mV/V, Full Bridge
AS–5B38004A
3 mV/V, Half Bridge
AS–5B38005A
2 mV/V, Full Bridge
NOTE: Isolated strain gauge input to 10 kHz bandwidth, all have 10.0 V excitation for bridges with resistance range of 300W to 10kW.
Wide Bandwidth (10 kHz) Analog Voltage Input Packs
The following table presents the part numbers and input ranges for the available wide bandwidth analog voltage input packs.
Part Number
Input Range
AS–5B40001A
0—10 mV
AS–5B40002A
0—50 mV
AS–5B40003A
0—100 mV
AS–5B40004A
-10— +10 mV
AS–5B40005A
-50— +50 mV
AS–5B40006A
-100— +100 mV
AS–5B41001A
0—1 V
AS–5B41002A
0—5 V
AS–5B41003A
0—10 V
AS–5B41004A
-1— +1 V
AS–5B41005A
-5— +5 V
AS–5B41006A
-10— +10 V
NOTE: Wide bandwidth input packs are only used for high-speed applications. They are more susceptible to external noise levels, and require careful routing and shielding of input signal leads.
Linear Thermocouple Input Packs
The following table presents the part numbers, types, and input ranges for the available linear thermocouple input packs.
Part Number
Type
Input Range
AS–5B47J01A
J
0—760°C (32—1400°F)
AS–5B47J02A
J
-100— +300°C (-148—572°F)
AS–5B47J03A
J
0—500°C (32—932°F)
AS–5B47K04A
K
0—1000°C (32—1832°F)
AS–5B47K05A
K
0—500°C (32—932°F)
AS–5B47T06A
T
-100— +400°C (-148—752°F)
AS–5B47T07A
T
0—200°C (32—392°F)
AS–5B47E08A
E
0—1000°C (32—1832°F)
AS–5B47R09A
R
500—1750°C (932—3182°F)
AS–5B47S10A
S
500—1750°C (932—3182°F
AS–5B47B11A
B
500—1800°C (932—3272°F)