B875–111 Analog Input, Specifications
(Original Document)
Specification Table
The following table provides the specifications for the unit.
B875-111 Specifications
Analog Inputs/Module
I/O mapped as B875-111
Eight differential
I/O mapped as B877-111
16 Single-ended
Input Ranges
Voltage
1—5 Vdc
0—5 Vdc
0—10 V
-5—+5 V
-10—+10 V
Current
4—20 mA
0—20 mA
-20—+20 mA
Input Analog Filter
Single pole low pass, with -3 dB cut-off frequency at 48 Hz 10%
Input Resistance
Current Mode
250 Ω, 0.05%
Voltage Mode
Within range > 10 MW, outside range 10,000 Ω
Input Resistance (No power)
Differential Inputs
20kΩ /channel
Single-ended Inputs
10 kΩ/channel
Input Protection
Normal Mode
120 V RMS differential input
Common Mode
120 V RMS
Throughput (T)
eight channels
10 ms without input sampling
16 channels
20 ms without input sampling
Over Current Protection
Up to 30 mA
Common Mode Range
2 V for 10 V, 7 V for 5 V
Rejection
-40 dB typical, dc to 60 Hz
Input Isolation
Input to OURBUS
1500 Vac RMS for 1 minute
Input to Case
1500 Vac RMS for 1 minute
Input to Input
25 Vac
Accuracy
0.1% absolute accuracy over temperature range
Conversion Resolution
All ranges
>12 bits
Bipolar
1 part in 15,000
Unipolar
1 part in 7,500
Unipolar with offset
1 part in 6,000
Linearity Error
0.05% of full scale over the operating range
Differential
Nonlinearity
0.006% of full scale over the operating range
Repeatability
0.025% of full scale RMS, constant temperature, no averaging
Output Range
Four selectable output formats
Output Averaging
Options are: N = 8, 16, and 32 samples to be averaged
Output Digital Filter, Fc
Single pole low pass with cut-off frequency dependent upon the number of averaged samples, N and T
Out-of-range Data
2.4% above and below range
Power Required
+5 V
500 mA
+4.3 V
900 mA
-5 V
0 mA
Terminal Connector
AS–8535–000
Reference Type
B875-111 Mapped as 8 registers input 3x
B877-111 Mapped as 16 registers input 3x
Input Type
BIN/BCD