B873-012 and B875-012 Specifications
(Original Document)
Module Specifications
The following table gives specifications for the B873-012 and B875-012 input modules.
Description
Analog input
-10 to +10 VDC
Number of Channels
4, (B873-012)
8, (B875-012)
Operating Range
-10 to +10 VDC
Impedance
0.5 MΩ per input
1 MΩ differentially
Resolution
13 bit
Filter
-3 dB @ 18 Hz
Rolloff -20 dB per decade
Linearity
+.05% of full scale @ 25 °C (77 °F)
Protection
240 VAC RMS
Common Mode
Range
Rejection
0 VAC to 30 VAC RMS
> -86 dB @ 60 Hz
Isolation
Channel to Channel
Input to Case
Module
250 VAC RMS
500 VAC RMS for one minute
1500 VAC RMS for one minute
300 VAC RMS continuous
Accuracy
Overall
At 25 °C (77 °F)
Offset Drift
Gain Drift
17.1 mV
1.2207 mV
100 μV per °C
55.6 μV per °F
+/-15 ppm per °C
+/-8.3 ppm per °F
Repeatability
Over a twenty-four hour period, with a constant voltage and at a constant operating temperature, the input data value will be within +/-2 counts.
Power Required
+5 V
+4.3 V
-5 V
300 mA
300 mA
0 mA
Data Format
0000
0001 to 8191
8192
Power Up
On diagnostic failure or during failure recovery
Under range
Valid
Over range
Throughput Rates
Update Interval
Out of Range
4 channels 400 ms
8 channels 710 ms
(Including diagnostics)
220 ms for each channel in under or over range condition
Terminal Connector
AS-8533-001 (B873-012)
AS-8533-002 (B875-012)
Reference Type
B873-012 Mapped as 4 registers 3x
B875-012 Mapped as 8 registers 3x
Input Type
BIN/BCD