Description
|
Analog output D/A; 4 - 20 mA
|
Number of Points
|
4
|
Operating Range
|
4 - 20 mA
|
Maximum Loop Supply Voltage
|
60 Vdc
|
Allowable Resistance Range*
|
|
Minimum
and
Maximum
|
Rmin = VLoop** - 30 V 0.02 A
Rmax = VLoop** - 7 V 0.02 A
|
*Resistance is the sum of all components, including wiring, in the field side circuit.
|
|
**VLoop equals the voltage of the loop supply (not to exceed 60 Vdc). If voltage is <30 Vdc, then the minimum loop resistance is 0 Ω. Refer to the Calibration Procedure (Method 2)
|
|
Voltage Drop @ 20 mA
|
|
Minimum
Maximum
|
7 Vdc
30 Vdc
|
Response Time to Within +/_0.1% of Full Range
|
35 mS, all four channels
|
Valid Data Values
|
0 thru 4095, or offset 4096-8191
|
Resolution
|
1 part in 4096 counts
|
Monitor Output Voltage
|
|
Range
|
1 to 5 Vdc
|
Min Load
|
1 MΩ
|
Impedance
|
470 Ω, typical
|
Accuracy***
|
|
Output Errors @ 25 °C (77 °F)
|
|
Overall
|
+/-0.1% @ 25 °C absolute
|
Nonlinearity
|
+/-0.024%
|
Differential Nonlinearity
|
+/-0.036%
|
*** All percentages are of full range.
|
|
Output Isolation
|
|
Output to OURBUS
|
1500 Vac or 2500 Vdc for 1 minute
500 Vac or 500 Vdc continuous operation
|
Channel to Channel
|
1500 Vac or 2500 Vdc for 1 minute
500 Vac or 500 Vdc continuous operation
|
Conversion
|
|
Resolution
Update Time
|
12-bits (1 part in 4096
The module can accept new data every 1 mS for a 4 channel update)
|
Settling Time
|
Within +/-0.1%, < 350mS
|
Linearity
|
0 to 60 °C, +/- 1 LSB maximum
|
Differential Nonlinearity
|
0 to 60 °C, +/- 1.5 LSB maximum
|
Load Inductance
|
1 Henry max, with no external diode suppression
|
Power Required
|
|
+5 V
+4.3 V
-5 V
|
475 mA
5 mA
0 mA
|
Terminal Connector
|
AS-8535-000
|
Reference Type
|
Mapped as 4 registers output 4x
|
Output Type
|