814–108 Specifications
|
||
---|---|---|
Description
|
Relay (NO/NC) output,
|
|
Number of Points
|
8
|
|
Operating Voltage
|
0—30 Vdc 0—240 Vac/47—63 Hz
|
|
Number of Groups
|
8
|
|
Outputs/group
|
1
|
|
ON Current
|
Maximum/point
|
5 A @ 30 Vdc/120 Vac
|
4 A @ 240 Vac
|
||
Maximum/module
|
40 A @ 30 Vdc/120 Vac
|
|
Maximum Load Current
|
Carrying (unswitched)
|
3 A max)
|
Switching
|
2.0 max (0.3 A @ 300 Vdc
|
|
Switching Capability
|
960 VA maximum, or 150 W dc maximum
|
|
Contact Resistance
|
< 300 mΩ (including fuse, wire, connectors, and contacts)
|
|
OFF State
|
Leakage Current
|
.5 mA (typical) @ 240 Vac/60 Hz
|
Maximum Response Time
|
OFF→ΟΝ
|
15 ms (6 ms typical)
|
|
ON→OFF
|
15 ms (6 ms typical)
|
Power Required
|
+5 V
|
107 mA
|
|
+4.3 V
|
800 mA
|
|
-5 V
|
0 mA
|
Relay Life Rating
|
100,000 operations, and 50,000 operations with inductive loads @ 25°C
|
|
Terminal Connector
|
AS-8534-000
|
|
Fusing
|
1 / output, 7 A
|
|
Reference Type
|
Mapped as 8 bits output
0x
or
Mapped as 1 register output
4x
|
|
Output Type
|
BIN/BCD
|