B820–008 10—60 Vdc Output, Specifications
(Original Document)
Specification Table
The following table provides the specifications for the unit.
B820–008 Specifications
Description
10—60 Vdc output
Type of Operation
True high
Number of Points
8
Operating Voltage
10—60 Vdc
Number of Groups
4
Outputs/group
2
On Current
Maximum/point
2 A
Maximum/module
12 A
Maximum/group
6 A
Surge Current
10 A/channel max for 10 ms at a repetition rate of 0.05%
ON State
Voltage Drop
1.5 Vdc max @ 2 A
OFF State
Leakage Current
5 mA (max) @ 60 Vdc
Peak Voltage
80 Vdc max for 10 ms at a repetition rate of 0.05%
Maximum Response Time
OFF→ΟΝ
1 ms (.1 ms typical)
ON→OFF
1 ms (.1 ms typical))
dv/dt
200 V/s
Power Required
+5 V
90 mA
+4.3 V
80 mA
-5 V
0 mA
External Power Supply
10—60 Vdc, 500 mA max./group (excluding field load current))
Terminal Connector
AS-8534-000
Fusing
One/group, 3 AG, 6 A (normal blow)
Reference Type
Mapped as 8 bits output
0x
or
Mapped as 1 register output
4x
Output Type
BIN/BCD