B820–008 Specifications
|
||
---|---|---|
Description
|
10—60 Vdc output
|
|
Type of Operation
|
True high
|
|
Number of Points
|
8
|
|
Operating Voltage
|
10—60 Vdc
|
|
Number of Groups
|
4
|
|
Outputs/group
|
2
|
|
On Current
|
Maximum/point
|
2 A
|
Maximum/module
|
12 A
|
|
Maximum/group
|
6 A
|
|
Surge Current
|
10 A/channel max for 10 ms at a repetition rate of 0.05%
|
|
ON State
|
Voltage Drop
|
1.5 Vdc max @ 2 A
|
OFF State
|
Leakage Current
|
5 mA (max) @ 60 Vdc
|
Peak Voltage
|
80 Vdc max for 10 ms at a repetition rate of 0.05%
|
|
Maximum Response Time
|
OFF→ΟΝ
|
1 ms (.1 ms typical)
|
|
ON→OFF
|
1 ms (.1 ms typical))
|
dv/dt
|
200 V/s
|
|
Power Required
|
+5 V
|
90 mA
|
|
+4.3 V
|
80 mA
|
|
-5 V
|
0 mA
|
External Power Supply
|
10—60 Vdc, 500 mA max./group (excluding field load current))
|
|
Terminal Connector
|
AS-8534-000
|
|
Fusing
|
One/group, 3 AG, 6 A (normal blow)
|
|
Reference Type
|
Mapped as 8 bits output
0x
or
Mapped as 1 register output
4x
|
|
Output Type
|
BIN/BCD
|