Description
|
24 Vdc high density monitored input
|
|
Type of Operation
|
True high
|
|
Number of Points
|
32
|
|
Operating Range Voltage
|
18-30 Vdc true high, 24 Vdc nominal
|
|
Number of Groups
|
2
|
|
Inputs/group
|
16
|
|
On State Conditions
|
18 Vdc minimum @ the input,
|
|
30 Vdc maximum @ the input,
|
||
Typical on state current: 4 mA
|
||
Off State Conditions
|
6 Vdc maximum @ the input,
|
|
Typical OFF state current: 1 mA
|
||
Maximum Response Time
|
OFF→ON
|
10 ms
|
ON →OFF
|
10 ms
|
|
Power Required
|
+5 V
|
0 mA
|
|
+4.3 V
|
0 mA
|
|
-5 V
|
0 mA
|
External Power Supply
|
Operating Current
|
20 mA of field power plus point input channel
|
Operating Voltage
|
18-30 Vdc true high, 24 Vdc nominal
|
|
Terminal Connector
|
AS-8535-000
|
|
Reference Type
|
Mapped as 64 bits input
1x
or
Mapped as 4 registers input
3x
|
|
Input Type
|
BIN/BCD
|