Description
|
24 Vdc diagnostic output
|
|
Type of Operation
|
True high
|
|
Number of Points
|
32
|
|
Operating Voltage
|
19.2-28 Vdc
|
|
Number of Groups
|
4
|
|
Outputs/group
|
8
|
|
ON State Voltage Drop
|
0.5 Vdc maximum @ 1 A
|
|
OFF State Leakage
|
1.0 mA maximum @ 28.0 Vdc
|
|
Minimum Load
|
100 mA
|
|
Maximum Continuous Current
|
per output
|
1.0 A
|
|
per group
|
6.0 A
|
|
per module
|
24.0 A
|
Surge Current
|
peak
|
7.5 A for 0.5 ms
|
|
maximum
|
10 pulses/s with 1.0 A dc
|
Load Inductance
|
1 H maximum with no external diode suppression
|
|
Load Capacitance
|
1000 f maximum
|
|
Flags B882 Only
|
Open Load
|
100 mA or less
|
Over Current
|
3.5 A or greater
|
|
Over Voltage
|
31 Vdc or greater
|
|
Over Temperature
|
140°C or greater
|
|
Maximum Response Time
|
OFF → ON
|
1 ms with a resistive load
|
|
ON → OFF
|
1 ms with a resistive load
|
Power Required
|
+5 V
|
300 mA*
|
|
+4.3 V
|
10 mA
|
|
-5 V
|
0 mA
|
* When all outputs are ON, +5 V = 300mA. When all outputs are OFF, +5 V = 200 mA.
|
||
External Power Supply
|
With nominal voltage of 24 Vdc re-quired to power the field side of the B882**
|
|
Terminal Connector
|
AS-8535-000
|
|
Reference Type
Inputs
|
Mapped as 32 bits input
1x
or
Mapped as 2 registers input
3x
|
|
Reference Type
Outputs
|
Mapped as 32 bits output
0x
or
Mapped as 2 registers output
4x
|
|
Output Type
|
BIN/BCD
|
|
** The external power supply must provide power to the field side loads and the field side electronics. The amperage sizing requirements of this supply have three components: 160 mA/group maximum (all channels ON), plus steady state load current of all outputs capable of being ON simultaneously, plus the inrush current of all outputs capable of being switched simultaneously.
|