B882–032 24 Vdc Diagnostic Output, Specifications
(Original Document)
B882-032 specifications
Description
24 Vdc diagnostic output
Type of Operation
True high
Number of Points
32
Operating Voltage
19.2-28 Vdc
Number of Groups
4
Outputs/group
8
ON State Voltage Drop
0.5 Vdc maximum @ 1 A
OFF State Leakage
1.0 mA maximum @ 28.0 Vdc
Minimum Load
100 mA
Maximum Continuous Current
per output
1.0 A
per group
6.0 A
per module
24.0 A
Surge Current
peak
7.5 A for 0.5 ms
maximum
10 pulses/s with 1.0 A dc
Load Inductance
1 H maximum with no external diode suppression
Load Capacitance
1000 f maximum
Flags B882 Only
Open Load
100 mA or less
Over Current
3.5 A or greater
Over Voltage
31 Vdc or greater
Over Temperature
140°C or greater
Maximum Response Time
OFF → ON
1 ms with a resistive load
ON → OFF
1 ms with a resistive load
Power Required
+5 V
300 mA*
+4.3 V
10 mA
-5 V
0 mA
* When all outputs are ON, +5 V = 300mA. When all outputs are OFF, +5 V = 200 mA.
External Power Supply
With nominal voltage of 24 Vdc re-quired to power the field side of the B882**
Terminal Connector
AS-8535-000
Reference Type
Inputs
Mapped as 32 bits input
1x
or
Mapped as 2 registers input
3x
Reference Type
Outputs
Mapped as 32 bits output
0x
or
Mapped as 2 registers output
4x
Output Type
BIN/BCD
** The external power supply must provide power to the field side loads and the field side electronics. The amperage sizing requirements of this supply have three components: 160 mA/group maximum (all channels ON), plus steady state load current of all outputs capable of being ON simultaneously, plus the inrush current of all outputs capable of being switched simultaneously.