B881–508 125 Vdc Output, Specifications
(Original Document)
B881–508, specifications
Description
125 Vdc true high output
Number of Points
8
Operating Voltage
5-140 Vdc maximum
Number of Groups
8
Outputs/group
1
Maximum Load Current
5.0 A continuous/channel maximum @ 25°C derated by 0.03 A/°C-4.0 A continuous per channel maximum @ 60°C 29.0 A/ module maximum
Pulsed ON Cycle
500 ms maximum for 5-30 A load
Inductance and Maximum Current/Channel
I 2 L < 25 W*
I 2 LF < 0.5 W**
Wattage
< 24 W, 2.5 W/point maximum
Minimum Load Current
75 mA
Surge Current
30.0 A 1 cycle (500 ms)/channel maximum
Minimum Load Current
75 mA
Maximum Response Time
OFF → ON
<75 S
ON → OFF
<100 S
Maximum OFF State Leakage Current
<3 mA
ON State Voltage Drop Across Module
< 0.75 Vdc @ 4 A Load Current
External Inputs
Response Time
75 S
Working Voltage Range
19.2-28 Vdc
Maximum Input Range
30 Vdc
Mode of Operation
True High
Power Required
+5 V
300 mA
+4.3 V
0 mA
-5 V
0 mA
External Power Supply
5-140 Vdc field power supply
Terminal Connector
AS-8535--000
Reference Type
Input
Mapped as 16 bits input
1x
or
Mapped as 1 register input
3x
Reference Type
Outputs
Mapped as 16 bits output
0x
or
Mapped as 1 register output
4x
Output Type
BIN/BCD
*Typical values of relay inductance and currents that can be switched safely at 1 s rates using this formula.
**For repetitive pulses, use this formula.
NOTE: Proper fusing of external circuitry is required, depending on the application.