B865–001 Register Input, Specifications
(Original Document)
Module B865–001, specification table
Description
TTL register input
Number of Points
8 channels, 16 data lines
Operating Voltage
5 V TTL
Number of Groups
NA
Outputs/group
NA
Guaranteed Min. Levels
High State>3.5 Vdc
Low State<0.4 Vdc while sinking 16 mA
Strobe Output Power
2 TTL loads @ 5 Vdc
Strobe Width Timing
2 mS 10%
Data Set-up Time
Within 180 s after the strobe has gone active (LO), data must have sta-bilized on the field side inputs
Minimum Data Hold Time
100 s must be provided by user
Maximum Response Time
OFF→ON
20 ms
ON →OFF
20 ms
Power Required
+5 V
400 mA
+4.3 V
600 mA
-5 V
0 mA
External Supply
A +5 Vdc external power supply is required for pull-up resistor VCC
Field Devices Requirements
Field Device
Output Level
TTL
Low: 0 < 0.8 Vdc @ 1.6 A
High: 1 > 2.4 Vdc @ 40 A
CMOS
Low: 0 < 1.6 Vdc @ 0.3 A
High: 1 > 3.3 Vdc @ 0.3 A
Terminal Connector
AS-8535-000
Reference Type
Mapped as 128 bits input
1x
or
Mapped as 8 registers input
3x
Input Type
BIN/BCD
NOTE: All user field devices must have outputs that feature latched, tri-state, or open collector, or wired or passive logic. The user must provide 2.2 kΩ 10% pull-up resistors for each strobe line.