Module Type
|
16 IN individually isolated
|
External Power
|
Not required for this module
|
Power Dissipation
|
2.0 W/0.30 W x the number of points ON
|
Bus Current required
|
400 mA
|
I/O map
|
1 input word
|
Fault Detection
|
None
|
LEDs
|
Active 1...16 (green)-indicates point status
|
ON (voltage)
|
15...30 Vdc
|
OFF (voltage)
|
-3...+5 Vdc
|
ON (current)
|
2.0...8.0 mA
|
OFF (current)
|
0...0.5 mA
|
Continuous
|
30 Vdc
|
30 Vdc reverse polarity (diode protection)
|
Point to Point
|
500 Vac rms for 1 minute
|
Point to Bus
|
1780 Vac rms for 1 minute
|
OFF - ON
|
30 μs (max)
|
ON - OFF
|
130 μs (max)
|
Internal
|
None
|
External
|
User discretion
|
Module Coding
|
ABE
|
Terminal Strip Coding
|
CDF
|