I, Q, M, K
|
X, W, D, F
|
r
|
.
|
m
|
.
|
c
|
.
|
i
|
.
|
j
|
---|---|---|---|---|---|---|---|---|---|---|---|
Symbol
|
Object type
|
Format
|
Rack
|
Module position
|
Channel no.
|
Rank
|
Word bit
|
Family
|
Element
|
Meaning
|
---|---|---|
Symbol
|
%
|
-
|
Object type
|
I
Q
|
Image of the physical input of the module.
Image of the physical output of the module.
This information is exchanged automatically for each cycle of the task to which they are attached.
|
M
|
Internal variable.
This read or write information is exchanged at the request of the application.
|
|
K
|
Internal constant.
This configuration information is available as read only.
|
|
Format (size)
|
X
|
Boolean.
For Boolean objects the X can be omitted.
|
W
|
Single length.
|
|
D
|
Double length.
|
|
F
|
Floating point.
|
|
Rack address
|
r
|
Rack address.
|
Module position
|
m
|
Module position number in the rack.
|
Channel no.
|
c
|
Channel no.
0 to 127 or MOD (MOD: channel reserved for managing the module and parameters common to all the channels).
|
Rank
|
i
|
Word rank.
0 to 127 or ERR (ERR: indicates an error in the word).
|
Word bit
|
j
|
Position of the bit in the word.
|
Object
|
Description
|
---|---|
%I1.3.MOD.ERR
|
Error information for the analog input module located in position 3 on rack 1.
|
%I1.4.1.ERR
|
Channel 1 error information for the analog input module located in position 4 on rack 1.
|
%IW1.2.2
|
Image word for the analog input 2 of the module located in position 2 on rack 1.
|
%QW2.4.1
|
Image word for the analog output 1 of the module located in position 4 on rack 2.
|