Hot Standby Safety CPU Specifics
Original instructions
Introduction
The 140 CPU 671 60S Quantum Safety CPU module is certified for use in Hot Standby SIL3 solutions compliant with the 61508 IEC standard. For more details about to the safety certifications, refer to the Modicon Quantum Safety PLC Safety Reference Manual.
In the Standalone Safety CPU, the Ethernet port is used to communicate with other devices using a normal Ethernet cable.
In the Hot Standby Safety CPU, the connection used to exchange data between the Primary CPU and the Standby CPU controller is a fiber optic link. Because the fiber optic link is not part of the Safety loop, the PFD and PFH values of the Hot Standby CPU are the same as those of the Standalone CPU.
Each Safety CPU can include a PCMCIA memory card, but its use and presence is not mandatory.
NOTE: This CPU cannot be used in a Quantum Ethernet I/O Hot Standby system.
Description of a Safety Hot Standby Configuration
The Hot Standby configuration contains two identical local racks and at least one remote I/O drop because I/Os cannot be placed in the local rack of a Safety Hot Standby configuration.
Besides a power supply module (there must be at least one 140 CPS 124 20 or one 140 CPS 22 400), each local rack must contain:
Besides a power supply, I/O modules (including at least one 140 CPS 124 20 or one 140 CPS 22 400), the remote drop(s) must include a 140 CRA 932 00 module.
CAUTION
UNINTENDED EQUIPMENT OPERATION
Use only high availability RIO modules with dual cabling in a Safety-Related System.
Failure to follow these instructions can result in injury or equipment damage.
Description of the Operating Modes
State Compatibility with Safe and Maintenance Modes
A Quantum Hot Standby system has two states:
Impact of the PLC Switchover on the Process Safety Time
If the Primary CPU detects an internal or external problem, it stops exchanging data with the Standby CPU and stops processing the I/O. As soon as the Standby CPU detects that there are no longer exchanges with the Primary CPU, it takes over the role of the Primary CPU, executing the user logic and processing the I/O. Therefore, the output modules must filter the lack of exchange with the Primary CPU to avoid glitches when a Switchover occurs. This is achieved by configuring the output module time-out. As a result, the PLC reaction time is greater than the time-out configured in the output module, thereby influencing the process Safety time.
NOTE: The behavior of the Hot Standby Safety CPU is equivalent to a Standalone Safety CPU.
In case of a detected error, the Safety PLC enters:
Availability of the Hot Standby Functions
In addition to the standard Hot Standby functions, you can use an EFB to program an automatic Switchover between Primary CPU and Standby CPU to verify the ability of the Standby CPU to take over from the Primary CPU. That means that the Standby CPU periodically becomes the Primary CPU and the Primary CPU becomes the Standby CPU.
It is recommended to avoid using the USB link during a Switchover.
The following table lists the available Hot Standby functions in Maintenance and Safety modes:
Function
Maintenance Mode
Safety Mode
Hot Standby
yes
yes
Switchover
yes
yes
EFB Swap
no
yes
Keypad
yes
yes
Application mismatch
yes
no
OS Upgrade
yes, if Standby CPU is in Stop Offline
no
Application Transfer
yes
no
NOTE: Applying the power simultaneously to Primary CPU and Standby CPU is allowed, but we recommend to do it sequentially.