140 CPS 524 00 Wiring Diagram
Original instructions
Wiring Diagram Figure
NOTE: When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG (2 mm2) or 2 - 16 AWG (1.5 mm2).
WARNING
UNINTENDED EQUIPMENT OPERATION
  • Use only compatible combinations of power supplies in the Quantum backplane as indicated in the following compatibility matrix.
  • Remove line power from this module prior to insertion or removal.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Compatibility Matrix
For proper operation, refer to this table:
Compatibility matrix
Summable models
140CPS11420
140CPS11410
140CPS21400
140CPS41400
140CPS11420
Yes
Yes
No
No
140CPS11410
Yes
Yes
No
No
140CPS21400
No
No
Yes
Yes
140CPS41400
No
No
Yes
Yes
Redundant models
140CPS12420
140CPS12400
140CPS22400
140CPS42400
140CPS52400
140CPS12420
Yes
No
Yes
Yes
No
140CPS12400
No
Yes
No
No
Yes
140CPS22400
Yes
No
Yes
Yes
No
140CPS42400
Yes
No
Yes
Yes
No
140CPS52400
No
Yes
No
No
Yes