Operating mode
|
Standalone
|
Redundant
|
|
Internal power dissipation (in W)
|
13 W
|
Network power consumption
|
Electric losses + (5.1 x Iout)1
|
1: Iout: sum of currents consumption by all modules in rack (in A)
|
Input voltage
|
100 ... 150 VDC (including ripple)
|
Input current
|
0.5 A @ 125 VDC
|
Inrush current
|
28 A @ 125 VDC
|
Input power interruption
|
1 ms max.
|
Fusing (external)
|
2 A slow-blow
|
Voltage
|
5.1 VDC
|
||
Max. Current
|
Standalone
|
8 A @ 60°C
|
|
Redudant
|
a) Two 140 CPS 524 00
|
8 A @ 60°C
|
|
b) Three 140 CPS 524 00
|
16 A @ 60°C
|
||
c) One 140 CPS 124 00 and one 140 CPS 524 00
|
8 A @ 60°C
|
||
d) One 140 CPS 124 00 and two 140 CPS 524 00
|
16 A @ 60°C
|
||
e) Two 140 CPS 124 00 and one 140 CPS 524 00
|
16 A @ 60°C
|
||
Min Current
|
Not Required
|
||
Protection
|
Over-current, over-voltage
|