 Step     
 | 
 Action     
 | 
|---|---|
| 
 1     
 | 
 Open the access flap on the front of the power supply module.     
 | 
| 
 2     
 | 
 Place the battery in its slot, taking care to respect polarities as marked on the module.     
 | 
| 
 3     
 | 
 Close the access flap.     
 | 

| 
 Step     
 | 
 Action     
 | 
|---|---|
| 
 1     
 | 
 Open the access flap for the battery.     
 | 
| 
 2     
 | 
 Remove the defective battery from its slot.     
 | 
| 
 3     
 | 
 Put the new battery into place.     
 | 
| 
 4     
 | 
 Close and lock the access flap.     
 | 

| 
 Ambient temperature when inoperative     
 | 
 ≤ 30°C     
 | 
 40°C     
 | 
 50°C     
 | 
 60°C     
 | 
|
|---|---|---|---|---|---|
| 
 Backup time     
 | 
 PLC off for 12 hours per day     
 | 
 5 years     
 | 
 3 years     
 | 
 2 years     
 | 
 1 year     
 | 
| 
 PLC off for 1 hour per day     
 | 
 5 years     
 | 
 5 years     
 | 
 4.5 years     
 | 
 4 years     
 | 
|
| 
 Ambient temperature when switching off     
 | 
 20°C     
 | 
 30°C     
 | 
 40°C     
 | 
 50°C     
 | 
|---|---|---|---|---|
| 
 Backup time     
 | 
 2h     
 | 
 45mn     
 | 
 20mn     
 | 
 8mn     
 |