 TSX FAN D2 P        
 | 
 TSX FAN A4P        
 | 
 TSX FAN A5P        
 | 
|
|---|---|---|---|---|
![]()  | 
![]()  | 
![]()  | 
||
| 
 Supply voltage       
 | 
 Nominal       
 | 
 24 VDC       
 | 
 110 VAC       
 | 
 220 VAC       
 | 
| 
 Limit       
 | 
 20..27.6 VDC       
 | 
 90120 VAC       
 | 
 180260 VAC       
 | 
|
| 
 Current consumed at nominal voltage       
 | 
 180 mA       
 | 
 180 mA       
 | 
 100 mA       
 | 
|
| 
 Temperature probe        
 | 
 Power supply voltage       
 | 
  direct 24/28 VDC or alternating 110/220 VAC       
 | 
||
| 
 Outage power (on resistive load)       
 | 
 1 A at 24 VDC / 10,000 operations       
 1 A at 48 VDC / 30,000 operations       
 1 A at 110 VDC / 30,000 operations       
 0.5 A at 220 VDC / 10,000 operations       
 | 
|||
| 
 Deactivation       
 | 
 Temperature>= 75°C +/- 5°C       
 | 
|||
| 
 Status       
 | 
  0.5 A at 220 VDC / 10,000 operations       
Temperature>= 75°C +/- 5°C       
 | 
|||
| 
 No. of modules per rack       
 | 
  | 
|||