Voltage limit when in use
|
Alternating current
|
19..0.264 V
|
||||
Direct current (possible up to 34V for 1hr in every 24hrs)
|
10...30 V
|
|||||
Thermal current
|
3 A
|
|||||
Alternating current load
|
Resistive load AC 12
|
Voltage
|
~24V
|
~48V
|
~110V
|
~220V
|
Power
|
50VAC (5)
|
50VAC (6)
110VAC (4)
|
110VAC (6)
220VAC (4)
|
220VAC (6)
|
||
Inductive AC14 and AC15
|
Voltage
|
~24V
|
~48V
|
~110V
|
~220V
|
|
Power
|
24VAC (4)
|
10VAC (10)
24VAC (8)
|
10VAC (11)
50VAC (7)
110VAC (2)
|
10VAC (11)
50VAC (9)
110VAC (6)
220VAC (1)
|
||
Direct current load
|
Resistive DC12
|
Voltage
|
24V (direct)
|
|||
Power
|
24 W (6)
40 W (3)
|
|||||
Inductive load DC13
(L/R=60ms)
|
Voltage
|
24V (direct)
|
||||
Power
|
10 W (8)
24 W (6)
|
|||||
Minimum switchable load
|
1mA/5V
|
|||||
Response time
|
Activation
|
< 10 ms
|
||||
Deactivation
|
< 10 ms
|
|||||
Type of contact
|
Normally open
|
|||||
Built-in protection
|
Against overloading and short circuits
|
None, a fast-blow fuse must be fitted
|
||||
Against inductive over-voltage in ~
|
None, compulsory installation – in parallel to the terminals of each pre-actuator - of a RC circuit or MOV (ZNO) peak limiter, appropriate to the voltage in use
|
|||||
Against direct current inductive over-voltage
|
None, a discharge diode must be fitted to the terminals of each pre-actuator.
|
|||||
Insulation (test voltage)
|
Contact/ground
|
2000 V rms-50/60Hz-1mn (on modules TSX PSY 2600/5500/1610/3610/5520)
|
||||
3000 V rms-50/60Hz-1mn (on module TSX PSY 8500)
|
||||||
Resistance of insulation
|
> 10 MΩ under 500 VDC
|