Compatibility with the Installed Base
(Original Document)
Summary Table
This table shows the compatibility with the installed base in relation to old and new references:
TSX RKY..E
TSX CBY..OK (•• 01)
TSX TLY (•• 01)
TSX RKY..E
TSX CBY..OK (•• 01)
TSX TLY A+B (•• 03)
TSX RKY..E
TSX CBY..OK (•• 02)
TSX CBY 1000
TSX TLY A+B (•• 03)
TSX RKY..EX
TSX CBY..OK (•• 02)
TSX CBY 1000
TSX TLYEX A/+/B
2 terminators
TSX TLY (•• 01)
YES
NO (1)
NO (1)
NO (3)
TSX CBY..OK cables (•• 01)
YES
YES
NO (2)
NO (4)
Terminators
TSX TLY A+B (•• 03)
YES
YES
YES
NO (3)
TSX RKY..E rack(s)
YES
YES
YES
NO (5)
TSX CBY..OK (•• 02) or CBY 1000 cable(s)
YES
YES
YES
YES
TSX RKY..EX rack(s)
NO (6)
YES
YES
YES
Terminators
TSX TLYEX A/+/B
YES
YES
YES
YES
Details of incompatibilities:
  1. Operation correct but incorrect detection of bus X break. Behavior of outputs not guaranteed for bus break.
  2. Correct operation for 50 instead of 100 meters. Correct detection of bus X break.
  3. Incorrect bus adaptation, no guarantee of operation. The TLY and TLY A/B adapt the signals in relation to 0V (wire in the bus X cable). The TLY EX A/B adapt the signals in relation to the shielding.
  4. Incorrect detection of duplicate address.
  5. Operation correct but no detection of duplicate address.
  6. Incorrect bus adaptation. TLY EX plugs required for correct operation when a TSXRKY..EX. is used in the configuration.
NOTE: In a PLC station, the TSX TLY line terminator torque must be of the same index.
•• corresponds to the product version.