Introduction
Use these instructions to map local slave instances in a network scanner to the enabled local slaves in the CPU’s embedded scanner service (
, , ).This example uses a BMENOC0301 Ethernet communication module as a network scanner (originator, O) that scans the CPU scanner service when it is enabled as a local slave (target, T).
Configure the BMENOC0301 module in an M580 Control Expert project.
Adding the Device DTM
Create a local slave instance that corresponds to an enabled local slave by name:
Step |
Action |
---|---|
1 |
Open your M580 Control Expert project. |
2 |
Right-click the BMENOC0301 module in the ( ) and select . |
3 |
Select the DTM that corresponds to the CPU. NOTE:
|
4 |
Press the button to open the dialog window. |
5 |
Assign a context-sensitive that corresponds to for the CPU.Example: BMEP58_ECPU_from_EDS_LS1 |
6 |
Click to see the local slave instance in the . |
Mapping Local Slave Numbers
In the M580 Control Expert project, associate the local slave instances in the BMENOC0301 scanner with specific local slaves that are enabled for the CPU’s scanner service:
Step |
Action |
---|---|
1 |
In the CPU target device (BMEP58_ECPU_from_EDS_LS1). , double-click the local slave instance that corresponds to in theNOTE: The default connection is , which
is most applicable to in the target device.
|
2 |
Select . |
3 |
Click to delete the connection to . |
4 |
Click to open the dialog box ( ). |
5 |
Select . |
6 |
Click . |
The local slave (
) is now the target of a local slave instance with a context-sensitive connection name ( ).Mapping IP Addresses
Associate the IP address of the local slave (target, T) with the local slave instances in the scanner (originator, O) configuration:
Step |
Action |
---|---|
1 |
Double-click the BMENOC0301 module in the . |
2 |
In the navigation pane, expand the Device List. |
3 |
Select a local slave instance (BMEP58_ECPU_from_EDS_LS1). |
4 |
Select the tab. |
5 |
In the 192.168.20.10). field, enter the IP address of the local slave device ( |
6 |
Click inside the navigation pane to make the button active.NOTE: You may have to select in the drop-down menu
( ) to activate the and buttons.
|
7 |
Configure the data size. |
8 |
Click . |
Configuring an Additional Connection
You have created one local slave instance that corresponds by name and IP address to an enabled local slave. This example uses two local slave connections, so make another connection for Local Slave 2.
Step |
Action |
---|---|
1 |
Repeat the preceeding steps to create a second local slave instance that corresponds to Local Slave 2. |
2 |
Build the Control Expert project. |
Accessing the Device DDT Variables
Step |
Actiom |
---|---|
1 |
In the Project Browser ( ), expand . |
2 |
Double-click to see the device DDTs that correspond with the CPU’s scanner service. |