Introduction
In a sample configuration, you will enable and .
First, use these instructions to enable in the CPU’s embedded scanner service configuration. At the end of this exercise, repeat these instructions to enable .
Enabling a Local Slave
Enable the CPU in the M580 local rack as a target device (local slave):
Step |
Action |
|---|---|
1 |
Open your M580 Control Expert project. |
2 |
On the tab, assign this to the CPU: BMEP58_ECPU_EXT. |
3 |
In the (), double-click the DTM that corresponds to the alias name of the BMENOC0301.2 module to open the configuration window. |
4 |
In the navigation pane, expand (+) to see the 3 available local slaves. |
5 |
Select a local slave to see its properties. (For this example, select .) |
6 |
In the drop-down list (), scroll to . |
7 |
Click to enable . |
8 |
Click to apply the changes and close the configuration window. |
You now have enabled for the CPU’s scanner service at IP address 192.168.20.10.
EtherNet/IP scanners that scan the network for the CPU’s scanner service at that IP address can use implicit messages to read from and write to the assembly instances that are associated with the local slave instance.
Enabling Another Local Slave
This example uses two local slave connections. Make a second connection for :
Step |
Action |
|---|---|
1 |
Repeat the steps above to enable a second local slave (). NOTE: The appropriate IP address for
this example (192.168.20.10) was already assigned
to the CPU’s scanner service in the assignment of .
|
2 |
Continue to the next procedure to configure the network scanner (originator, O). |

