Arrange devices in zones of differing disturbance climates
Zones of differing disturbances climates must be defined within the plant in which devices are arranged according to their sensitivity or potential for interference.
These include fundamentally different zones:
Process
Control system
Data processing with computer work stations
PLC system
Separation of the PLC system is enabled by being installed in cabinets or on machine chassis. The guidelines for cabinet setups can be found in Guidelines for Arranging the Device in the Cabinet or a Machine.
Process
The processing plant with interfering components forms its own zone.
Sensitive cables and devices for process data acquisition and control (that are always in this zone) must be shielded.
Strong interference affects high current equipment above all through their magnetic fields, such as:
High current equipment in energy supply company systems
Melting in chemical plants
Transformers
Energy distribution from manufacturing plants
Computer work stations
Computer work stations should be placed in separate, shielded rooms that are equipped with close-mesh equipotential bonding in the floor, see Guidelines for the Grounding System in Buildings.
In reality, it is often necessary to install computer work stations near the production line. Monitors near high current equipment can have such large problems with interference that work is no longer possible with them.
If the magnetic fields present exceed the values recommended for monitor use, counter measures must be taken such as:
Increase the distance from the source of the interference
Shielding of the source of interference
Use of plasma monitors
Shielding of monitor screens