Static Discharge
Very long bus cables, which have been laid but not yet connected, are discharged as follows:
Step |
Action |
---|---|
1 |
Select the PROFIBUS DP connector closest to the FE/PE grounding clamp. |
2 |
Touch the metal of the connector housing to the cabinet's FE/PE grounding clamp to discharge any static electricity. |
3 |
Now connect the bus connector to the device. |
4 |
Discharge the other PROFIBUS DP cable connectors as described in steps 2 and 3. |
Notes
NOTE: During mounting, the metal part of the PROFIBUS DP connector is connected
internally to the cable shield. When the bus cable connector is inserted
into the module’s PROFIBUS port, a short connection between
the shield and the FE/PE is created automatically.