Overview
Recently revised to meet new Interbus standards for electrical noise immunity, select Momentum products have been updated with an additional ground screw. This second ground screw is being added to all new and upgraded Momentum products. Currently, four communication adapters have been updated. They are:
Momentum Interbus Communication Adapter (170 INT 110 03), which supports the diagnostic functions of a Generation 4 Interbus Master and is compliant with Interbus certification, version 2
Momentum Ethernet Communication Adapter (170 ENT 110 01), version 2
Momentum Ethernet Communication Adapter (170 ENT 110 02), version 1
Momentum FIP IO Communication Adapter (170 FNT 110 01), version 2
These communication adapters contain a new grounding system, which was originally required to meet the revised Interbus electrical noise immunity standard (ability to pass a 2.2kv electrical fast transient burst test). This grounding system includes a male-female standoff and screw in the communication adapter, which is connected to a fixed standoff-ground nut on the printed circuit board on selected Momentum I/O modules.
Momentum I/O Modules
The Momentum I/O modules include the fixed standoff-ground nut assembly. The male-female standoff and ground screws are found in the redesigned communication adapters.
Name |
Description |
---|---|
170 AAI 030 00 |
8 Channel Differential Analog Input Module |
170 AA1 140 00 |
16 Channel Single-Ended Analog Input Module |
170 ADI 340 00 |
24 VDC 16 Point Input Module |
170 ADI 350 00 |
24 VDC 32 Point Input Module |
170 ADM 350 10 |
24 VDC 16 Point Input / 16 Point Output Module |
170 ADM 350 11 |
24 VDC 16 Point Input / 16 Point Output Fast Response Module |
170 ADM 350 15 |
24 VDC True Low 16 Point Input / Output Module |
170 ADM 370 10 |
24 VDC 16 Point Input / 8 Point Output @ 2 Amps Module |
170 ADM 390 10 |
24 VDC 16 Point Input / 12 Point Output Monitored Module |
170 ADM 390 30 |
24 VDC 10 Point Input / 8 Point Relay Output Module |
170 ADM 390 31 |
24 VDC 10 Point Input / 8 Point Relay Output Module |
170 ADM 850 10 |
10 to 60 VDC 16 Point Output Module |
170 ADO 340 00 |
24 VDC 16 Point Output Module |
170 ADO 350 00 |
24 VDC 32 Point Output Module |
170 ADO 830 30 |
6 Point Relay Output Module |
170 AEC 920 00 |
High Speed Counter Module |
170 AMM 090 00 |
4 Point Analog Input / 2 Point Analog Output - 4 Point Digital Input / 2 Point Digital Output Module |
170 AMM 090 01 |
4 Point Analog Input / 2 Channel Output 12 VDC Module |
170 AMM 110 30 |
2 Point Analog Input / 2 Point Analog Output - 16 Point Digital Input / 8 Point Digital Output Module |
170 ANR 120 90 |
6 Point Analog Input / 4 Point Analog Output - 8 Point Digital Input / 8 Point Digital Output Module |
170 ANR 120 91 |
6 Point Analog Input / 4 Point Analog Output - 10/10V 8 Point Digital Input/Output Module |
170 ARM 370 30 |
24 VDC 10 Point Input / 8 Point Output Module (120 VAC powered) |
Required Tools
The only tool required to install the ground screw is a PZ 2 Phillips head screwdriver. The recommended maximum torque on the ground screw is 0.5 Nm (4.4 in/lb).
Installation
CAUTION | |
---|---|
To install the ground screw, follow the steps below. Refer to the figure below for the screw locations.
Step |
Action |
---|---|
1 |
Install the standoff into the threaded fixed standoff-ground nut assembly, which is located on the I/O module’s printed circuit board. |
2 |
Snap the communication adapter onto the I/O module. Follow the same procedure as all other Momentum products. (For more information on communication adapter assembly, refer to the Modicon Momentum I/O Base User Guide (870 USE 002). |
3 |
Install the ground screw through the top of the communication adapter. |
Ground screw installation:

Backward Compatibility
The above I/O modules can also be used with any of the Momentum communication or processor adapters that do not include the ground screw.