Feature
|
Availability
|
Improvement
|
Description
|
---|---|---|---|
Improved Timeout and Retry Transmission algorithm
|
Control Expert
Concept
ProWORX
|
Improves TCP connection management
|
2004 version uses a variable timeout. Older versions used a fixed timeout.
Difference: Faster retransmission rates
|
Enable/Disable I/O Scanner entry
|
Control Expert
Concept
|
Reduces network traffic volume
|
Use the ‘Device Control Block’
Note: Concept Users
Concept uses diagnostic words.
Set = FF Disable channel
|
Send Modbus requests across a router
|
Control Expert
Concept
ProWORX
|
Allows routers to connect remote I/O devices to a controller
|
Automatic
|
Dynamic TCP port allocation
|
Control Expert
Concept
ProWORX
|
Improves connection/disconnection performance
|
Reserves TCP client ports 3072 (0xC00) through 4992 (0x1380)
Allocates ports dynamically
|
Repetitive rate display
|
Control Expert
|
Check status using GUI
|
Status displays in I/O Scanning tab of module editor
|
Parameter
|
Value
|
---|---|
Max. No. of Devices
|
64: 140 NOE 771 00 (Version 2.2 or earlier)
128: 140 NOE 771 00 (Version 3.0 or later), 140 NOE 771 01, and 140 NOE 771 11 only
128: HE CPU 651 x0
|
Max. No. of Input Words
|
4000
|
Max. No. of Output Words
|
4000
|
Health Timeout Value
|
User configured: 1...65535 ms in 1 ms increments
|
Last Value (Input)
|
User configured (zero or Hold)
|
IP Address
|
User configured
IP address of scanned device (Slave IP)
|
Local and Remote Register Reference
|
User configured
|
Repetitive Rate
|
User configured: 0...65535 in multiples of:
|
Unit ID
|
User configured
Configure ID only if using a bridge
|
Operation through a bridge
|
Modbus bridge: Supported
|
Modbus Plus bridge: Supported
|
|
Gateway/Bridge Device
|
Select the check box if you are using a bridge or a gateway device.
|