Rank
|
Input Type
|
|---|---|
|
24 Vdc
|
IEC type 2
|
|
48 Vdc
|
IEC type 3
|
|
60 Vdc
|
|
|
110 Vdc
|
UOFF(max) = 22 V; UON(min) = 79 V; UON(max) = 138 V
IOFF(max) = ION(min) = ION(max) ≈ 1.2 mA
|
|
125 Vdc
|
UOFF(max) = 25 V; UON(min) = 91 V; UON(max) = 156 V
IOFF(max) = ION(min) = ION(max) ≈ 1.25 mA
|
|
Definition
|
Pin Number
|
Definition
|
|
|---|---|---|---|
|
DCF_IN
|
2
|
1
|
IRIG+
|
|
DCF_COM
|
4
|
3
|
IRIG-
|
|
NC
|
6
|
5
|
NC
|
|
I1
|
8
|
7
|
I0
|
|
I3
|
10
|
9
|
I2
|
|
I5
|
12
|
11
|
I4
|
|
I7
|
14
|
13
|
I6
|
|
I9
|
16
|
15
|
I8
|
|
I11
|
18
|
17
|
I10
|
|
I13
|
20
|
19
|
I12
|
|
I15
|
22
|
21
|
I14
|
|
NC
|
24
|
23
|
NC
|
|
UB+
|
26
|
25
|
0 VDC
|
|
UB+
|
28
|
27
|
0 VDC
|
WARNING |
|
UNEXPECTED BEHAVIOR OF APPLICATION
The wrong wiring will cause death, serious injure, or equipment damage.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|

CAUTION |
|
LOSS OF INPUT FUNCTION
The power supply to the sensors for I0...I15 must be wired to UB+ and 0VDC pins even if the supply monitoring function is not needed.
Failure to follow these instructions can result in injury or equipment damage.
|
|
Internal
|
None
|
|
External
|
Fast blow fuse of 0.5 A
|
CAUTION |
|
LOSS OF INPUT FUNCTION
Install the correct rating and type of fuse.
Failure to follow these instructions can result in injury or equipment damage.
|