Specification
Original instructions
Specifications Table
Specifications for the Quantum 140 DIO 330 00 Intrinsically Safe Digital Output module are as follows.
Number of Output Points
8 OUT
Output Voltage
24 V (open)
Maximum Load Current
Each Point
45 mA
Per Module
360 mA
Off State Leakage/Point
0.4 mA
Response (Resistive Loads)
OFF-ON
1 ms
ON-OFF
1 ms
Output Protection (Internal)
Transient voltage suppression
Isolation
Channel to Channel
None
Channel to Bus
1780 VAC, 47-63 Hz or 2500 VDC for 1 min.
Fault Detection
None
Bus Current Required
2.2 Amp (full load)
Power Dissipation
5 W (full load)
External Power
Not required
Hot Swap
Not allowed per intrinsic safety requirements
Fusing
Internal - not user accessible