Specifications
Original instructions
General Specifications
Specifications for the Quantum 140 AII 330 10 Intrinsically Safe Current Input module are as follows.
Number of Channels
8 IN
Current Input
Linear Measuring Range
4 ... 20 mA
0 ... 20 mA
0 ... 25 mA
Absolute Maximum Input
25 mA internally limited
Input Impedance
100 ohms +/- 0.1% between V- and signal terminals
Resolution
4 ... 20 mA, 0 to 4,095 counts
4 ... 20 mA0 to 16,000 counts
0 ... 20 mA, 0 to 20,000 counts
0 ... 25 mA, 0 to 25,000 counts
Available Voltage
Terminals V+, V- :~ 14.5 Vdc at 25 mA
Terminals V+, Signal : ~ 13.6 Vdc at 20 mA
Accuracy Error @ 25°C
Typical: +/- 0.05% of full scale
Maximum: +/- 0.1% of full scale
Linearity
+ 0.003% of full scale
Accuracy Drift w/ Temperature
Typical: +/- 0.0025% of full scale /°C
Maximum: +/- 0.005% of full scale /°C
Common Mode Rejection
> 100 dB @ 50/60 Hz
Input Filter
Single pole low pass, -3 dB cutoff @ 15 Hz, +/- 20%
Isolation
Channel to Channel
None
Channel to Bus
1780 Vac @ 47-63 Hz or 2500 Vdc for 1 min.
Update Time
750 ms for all channels
Fault Detection
Broken wire (4 ... 20 mA mode)
Bus Current Required
1.5 A
Power Dissipation
7.5 W
External Power
Not required
Hot Swap
Not allowed per intrinsic safety standards
Fusing
Internal, not accessible