Module Type
|
32 OUT (4 groups x 8 points)
|
External Power
|
10 ... 30 VDC
|
Power Dissipation
|
2.5 W + 0.1 W x input points ON + 0.4 V x total load Currents
|
Bus Current required (Module)
|
500 mA
|
I/O map
|
2 input word
2 output word
|
Fault Detection
|
Blown fuse detect, loss of field power, incorrect output state.
|
Operating Voltage (max.)
|
10 ... 30 VDC
|
Absolute Voltage (max.)
|
50 VDC for 1.0 ms decaying voltage pulse
|
ON State Drop / Point
|
0.4 VDC @ 0.5 A
|
Each Point
|
0.5 A
|
Each Group
|
4.0 A
|
Per Module
|
16 A
|
OFF State Leakage / Point
|
0.4 mA @ 30 VDC
|
Surge Current (max.)
|
Each Point: 2.5 A @ 1 ms duration (no more than 6 per minute)
|
Load Inductance (max.)
|
0.5 Henry @ 4 Hz switch frequency, or:
![]() |
Load Capacitance (max.)
|
75 mF
|
Tungsten Load (max.)
|
2.5 W @ 10 VDC
3 W @ 12 VDC
6 W @ 24 VDC
|
Group to Group
|
500 VAC rms for 1 minute
|
Group to Bus
|
1780 VAC rms for 1 minute
|
Output Protection
|
Transient Voltage Suppression (internal), overload (short circuit) protecton
|
OFF - ON
|
1 ms (typical), 2 ms (max.)
|
ON - OFF
|
1 ms (typical), 2 ms (max.)
|