Module Type
|
32 OUT (4 groups x 8 points)
|
External Power
|
19.2 ... 30 VDC
|
Power Dissipation
|
5 W (all points ON)
|
Bus Current required (Module)
|
250 mA (max.)
|
I/O map
|
2 output word
|
Fault Detection
|
Group indication: loss of field power.
|
Operating Voltage (max.)
|
19.2 ... 30 VDC
|
ON State Drop / Point
|
0.5 VDC @ 0.5 A
|
Each Point
|
0.5 A
|
Each Group
|
4 A
|
Per Module
|
16 A
|
Surge Current (max.)
|
2 A each point (internally limited)
|
OFF State Leakage / Point
|
< 0.1 mA @ 24 VDC
|
Group to Group
|
500 VAC rms for 1 minute
|
Output to Bus
|
500 VAC rms for 1 minute
|
Output Protection (internal)
|
Thermal overload and short circuit.
|
OFF - ON
|
< 0.1 ms
|
ON - OFF
|
< 0.1 ms
|
Load Inductance (max.)
|
0.5 Henry @ 4 Hz switch frequency, or:
![]() |
Load Capacitance (max.)
|
50 μF
|