Original instructions
General Specifications
General Specifications
Module Type
4 Channel IN
2 Channel OUT (isolated)
External Power
Loop Voltage:... 30 VDC, up to 60 VDC with an external resistor
Bus Current required (Module)
350 mA
Error Detection
Open circuit in 4 ... 20 mA range, or over range, or under range in bipolar modes only.
Operating Ranges
Operating Ranges
Bipolar
+/- 10 VDC
+/- 5 VDC
+/- 20 mA
Unipolar
0 ...10 VDC
0 ... 5 VDC
0 ... 20 mA
Unipolar with Offset
1 ... 5 VDC
4 ... 20 mA
Voltage / Input
Voltage / Input
Operating Voltage (Channel to Channel)
+/- 40 VDC (max.)
Absolute Voltage (max.)
+/- 50 VDC
Linear Mesuring Range
2.4% over and under range
Input Impedance in Range
> 10 Mohms
Input Impedance over Range
< 0.5 Mohms
Current / Input
Current / Input
Absolute Current (max.)
+/- 25 mA
Linear Measuring Range
2.4% over and -9.6% under range.
Input Impedance
250 ohms
When configured for current inputs (jumper installed between IN(+) and SENSE terminals), a broken field wire results in a zero current reading.
If 4 ... 20 mA is selected, error LEDs and warning/out of range are displayed.
Resolution / Conversion
Resolution / Conversion
16 bit
+/- 10 VDC, 0 ...10 VDC
15 bit
+/- 5 VDC, 0 ...5 VDC, +/- 20 mA, 0 ... 20 mA
14 bit
1 ... 5 VDC; 4 ... 20 mA
Absolute Accuracy Error @ 25 degrees C
Voltage mode:
  • Typical: +/- 0.03% of full scale
  • Maximum: +/- 0.05% of full scale
Current mode:
  • Add an extra +/- 0.03% to voltage specification
Linearity
Monotonic +/- 1 LSB
Offset 0 ... 60 degrees C
+/- 0.0014% of full scale max.
Gain Shift 0 ... 60 degrees C
+/- 0.002% of full scale max.
Common Mode Rejection
Better than 80 dB @ 50 or 60 Hz
Input Filter
Single pole low pass, -3 dB @ 21 Hz, +/- 20%
Update Time
320 ms for 4 channels
Isolation
Isolation
Channel to Bus
500 VAC rms for 1 minute
750 VDC rms for 1 minute
Channel to Channel
500 VAC rms for 1 minute
750 VDC rms for 1 minute
Linear Measuring Ranges Table
The following table shows the linear measuring ranges for the Inputs.
Data Format
Input
Under Range
Normal
Over Range
16-bit Format
+/- 10 V
< 768
768 ... 64768
> 64768
+/- 5 V, +/- 20 mA
< 16768
16768 ... 48768
> 48768
0 ... 10 V
0 ... 64000
> 64000
0 ... 5 V, 0 ... 20 mA
0 ... 32000
> 32000
1 ... 5 V, 4 ... 20 mA
<6400
6400 ... 32000
> 32000
Voltmeter* Format
+/- 10 V
< -10000
-10000 ... 10000
> 10000
+/-5 V
< -5000
-5000 ... 5000
> 5000
0 ... 10 V
0 ... 10000
> 10000
0 ... 5 V
0 ... 5000
> 5000
1 ... 5 V
< 1000
1000 ... 5000
> 5000
+/- 20 mA
< 1000
-20000 ... 20000
> 20000
0 ... 20 mA
0 ... 20000
> 20000
4 ... 20 mA
< 4000
4000 ... 20000
> 20000
12-bit Format
+/- 10 V
0
0 ... 4095
4095
+/- 5 V, +/- 20 mA
0
0 ... 4095
4095
0 ... 10 V
0 ... 4095
4095
0 ... 5 V, 0 ... 20 mA
0 ... 4095
4095
1 ... 5 V, 4 ... 20 mA
0
0 ... 4095
4095
* The Voltmeter ranges are listed in Modsoft signed format.
Fuses
Fuses
Internal
Not required
External
User installed per local and national electrical codes
Output Specifications
Output Specifications
Loop Voltage
... 30 VDC, up to 60 VDC with an external resistor
Loop Resistance
* = ( - 30 VDC) / 0.020 A
= ( - 7 VDC) / 0.020 A
* No is required for loop voltage less than 30 VDC
Internal Voltage Drop
7 VDC min., 30 VDC max. @ 20 mA
Fault Detection
Open circuit in 4 ... 20 mA range, or over range, or under range in bipolar modes only.
Resolution / Conversion
Resolution / Conversion
Resolution
12 bit
Accuracy Error at 25 degrees C
+/- 0.20% of full scale
Accuracy Error @ 0 ...60 degrees C (voltage mode)
Typical: +/- 0.004% of full scale
Maximum: +/- 0.07% of full scale
Linearity
Monotonic +/- 1 LSB
Update Time
15 ms for 2 Channels
Settling time
900 micro sec to +/- 0.1 % of final value
Fault Detection
Open circuit indicator light and status byte
A range warning is issued when a channel input is outside the rated input value. Warning bits stay on after out of range bits are set. An out-of-range bit is set when a channel input exceeds the rated input value by 2.4%. Out of range bits are also set if inputs drop below 0.5V (1 ... 5V mode) or 2.08 mA (4 ... 20 mA mode)
Isolation
Isolation
Channel to Bus
500 VAC rms for 1 minute
750 VDC rms for 1 minute
Channel to Channel
500 VAC rms for 1 minute
750 VDC rms for 1 minute
Voltmeter Monitor Specifications Table
The following table shows the specifications for the voltmeter monitor for the analog input/output module.
Range
1 ... 5 V (Loop current must be active)
Scaling
(mA) x 0.250 = (volts)
Output Impedance
300 ohms typical
Maximum Wire Length
1 meter