Module Type
|
16 IN (1 group x 16 points)
|
Logic
|
True High
|
External Power
|
24 VDC (19.2 .. 30 VDC)
|
Power Dissipation
|
2.75 W + 0.25 W x the number of ON points
|
Bus Current Required
|
550 mA
|
I/O map
|
7 input words
|
Fault Detection
|
|
Update Time
|
15 ms for all channels
|
Group to Group
|
N/A
|
Group to Bus
|
1 500 VAC rms for 1 minute
|
ON Level voltage
|
+11 ... +30 VDC
|
OFF Level voltage
|
-3 ... +5 VDC
|
ON Level current
|
3.0 mA (min.)
|
OFF Level current
|
1.5 mA (max.)
|
Internal input impedance
|
3.675 kohms
|
Input Protection
|
By internal rectifier
|
Continuous
|
30 VDC
|
OFF - ON
|
25 ms (max.)
|
ON - OFF
|
25 ms (max.)
|
Internal
|
None
|
External
|
1 A fast blow fuse mandatory
|
![]() |
OVERCURRENT TO THE INPUTS
Use fast acting fuses to protect the electronic components of the module from overcurrent. Improper fuse selection could result to damage to the module.