Safety functions
|
SS ESD and PS monitoring
|
Yes (1 to 12 single or double contacts)
|
Moving cover monitoring
|
Yes (de-synchronization > 400 ms)
|
|
Sensitive conveyor monitoring
|
No
|
|
I-manual control
|
No
|
|
Safety characteristics
|
Refer to Functional Safety Certification
|
|
External module power supply
A1-A2 terminal
|
Voltage
|
24 Vdc
|
Residual ripple
|
5%
|
|
Voltage limit
|
-20%...+25%
|
|
F1 fuse external supply protection (according to IEC 947-5-1)
|
< 1A (gL)
|
|
Maximum consumption
|
200 mA
|
|
Check threshold
|
< 19 Vdc
|
|
Maximum current call
|
0.5 A / 1 ms
|
|
safety circuit voltage
|
24 Vdc
|
|
Module protection
|
Internal electronic fuse > 250 mA and < 1 A
|
|
Insulation
|
Over-voltage category II (2 kV), pollution degree 2
|
|
Power dissipated in the module
|
< 5 W
|
|
Dimensions
|
H x W x D
|
150 x 36 x 120 mm
|
Weight
|
0.43 kg
|
No. of safety channels
|
12 single or double SS ESDs
|
Reactivation / On button
|
Yes (S33-S34)
|
Single or double SS ESD selection
|
Yes with external shunt (B1)
|
Feedback loop
|
Yes (Y1-Y2)
|
Reactivation input monitoring
|
Yes with external shunt (Y3-Y4)
|
Call current
|
0,5 A / 1 ms
|
Input / Ground insulation
|
1000 Vrms actual 50/60 Hz - 1 min
|
Potential reference
|
None
|
|
Number and type of circuits
|
2
Circuits normally open with independent supplies
|
|
Rated voltage
|
24...240 Vac/24...125 Vdc
|
|
Outputs protected by fuses (compliant with EN VDE 0660 section 200 and IEC 60947-5-1
|
4 A (gL)
|
|
Rated thermal current
|
2 A (maximum 2.5 A)
|
|
ES request response time
|
< 12 ms
|
|
Mechanical durability
|
107 operations
|
|
Type of contact
|
Gold plated, AgSnO2 + 2 μm Au
|
|
Electrical durability
|
105 operations (with a normal load)
|
|
Output / Ground insulation
|
300 Vac insulation voltage compliant with VDE 0110, Section 1
|
Operating temperature
|
of the API
|
Temperature ranges:
|
of the cabling accessory
|
-10...60°C
|
|
Humidity without condensation
|
5...95%
|
|
Storage temperature
|
-25...70°C
|
|
Insulation resistance
|
> 10 MΩ under 500 Vdc
|
|
Dielectric strength on Sub-D compliant with EN IEC 61131
|
500 Vrms, 50/60 Hz, 1 min
|
|
Operating altitude
|
0...2000 m (0...6562 ft)
|
|
Degree of protection compliant with IP IEC 60529
|
Terminals/Unit
|
IP20
|
Place of installation
|
IP54
|
|
Maximum capacity of screw terminal blocks
|
2 x 1 mm2 wires with termination,
|
|
Tightening torque
|
0.5 N•m
|
Specific for PLCs
|
EN 61131-2 (IEC 61131-2), CSA 22-2 No. 142, UL508
|
Electrical equipment on machines
|
EN 60204-1 (IEC 60204-1)
|
Emergency stop equipment
|
EN ISO 13850
|
Machine safety: Safety-related part of control systems
|
EN ISO 13849-1 and -2
|