The TSX DMY 28RFK module
|
24 VDC positive logic inputs
|
||
Nominal input values
|
Voltage
|
24 VDC
|
|
Current
|
3.5 mA
|
||
Threshold input values
|
at 1
|
Voltage
|
≥ 11 V
|
Current
|
≥ 3 mA
|
||
at 0
|
Voltage
|
≤ 5 V
|
|
Current
|
≤ 1.5 mA
|
||
Sensor supply (including ripple)
|
19..30 V (possibly up to 34 V, limited to 1 hour every 24 hours)
|
||
Input impedance
|
at nominal U
|
6.3 kOhms
|
|
Response time
|
by default
|
4 ms
|
|
configurable filtering
|
0.1..7.5 ms (in 0.5 ms steps)
|
||
IEC 1131-2 compliance
|
type 1
|
||
IEC 947-5-2
|
|||
Dielectric strength
|
Input / ground or Input / internal logic
|
1500 V actual, 50 / 60 Hz for 1 min
|
|
Insulation resistance
|
> 10 MOhms (below 500 VDC)
|
||
Type of input
|
current sink
|
||
Paralleling of inputs (1)
|
yes
|
||
Sensor voltage check threshold
|
OK
|
> 18 V
|
|
Error
|
< 14 V
|
||
Check response time
|
on appearance
|
8 ms < T < 30 ms
|
|
on disappearance
|
1 ms < T < 3 ms
|
||
5 V consumption
|
typical
|
300 mA
|
|
maximum
|
350 mA
|
||
Sensor supply consumption (2)
|
typical
|
20 mA + (3.5 x Nb) mA
|
|
maximum
|
30 mA + (3.5 x Nb) mA
|
||
Dissipated power (2)
|
1.2 W + (0.1 x Nb) W
|
||
The characteristics at 60° are guaranteed for 60 % of inputs set to 1
|
|||
Legend:
|
|||
(1)
|
This characteristic is used to connect several inputs to the same module in parallel, or to different modules for input redundancy.
|
||
(2)
|
Nb = number of channels at 1.
|
The TSX DMY 28RFK module
|
24 VDC positive logic transistor outputs
|
||
Nominal values
|
Voltage
|
24 VDC
|
|
Current
|
0.5 A
|
||
Threshold values (1)
|
Voltage (including ripple)
|
19..30 V (34 V possible for 1 hour every 24 hours)
|
|
Current/channel
|
0.625 A
|
||
Current/module
|
4 A
|
||
Power of tungsten filament lamp
|
Maximum
|
6 W
|
|
Leakage current
|
at 0
|
< 1 mA
|
|
Voltage drop
|
at 1
|
< 1.2 V
|
|
Load impedance
|
minimum
|
48 Ohms
|
|
Response time (2)
|
0.6 ms
|
||
Frequency of switching to inductive load
|
0.5 / LI2 Hz
|
||
Paralleling of outputs
|
Yes (maximum of 2)
|
||
Compatibility with IEC 1131-2 DC inputs
|
Yes (type 1 and type 2)
|
||
Built-in protection
|
against over-voltage
|
Yes, by Transil diode
|
|
against inversions
|
Yes, by inverted diode (3)
|
||
against short-circuits and overloads
|
Yes, by current limiter and electric circuit-breaker 1.5 In < Id < 2 In
|
||
Pre-actuator voltage check threshold
|
OK
|
> 18 V
|
|
Error
|
< 14 V
|
||
Check response time
|
on appearance
|
T < 4 ms
|
|
on disappearance
|
T < 30 ms
|
||
24 V pre-actuator consumption (4)
|
typical
|
40 mA
|
|
maximum
|
60 mA
|
||
Dissipated power (5)
|
2.4 W + (0.75 x Nb) W
|
||
Dielectric strength
|
Output / ground or Output / internal logic
|
1500 V actual, 50 / 60 Hz for 1 min
|
|
Insulation resistance
|
> 10 MOhms (below 500 VDC)
|
||
The characteristics at 60 °C are guaranteed for 60 % of max. module current
|
|||
Legend:
|
|||
(1)
|
For U ≤ 30 V or 34 V.
|
||
(2)
|
All the outputs are equipped with fast electromagnet demagnetization circuits. Electromagnet discharge time < L/R
|
||
(3)
|
Fit a fuse to the +24 V pre-actuator supply.
|
||
(4)
|
Excluding load current.
|
||
(5)
|
Nb = number of outputs at 1.
|