TSX DSY 32T2K module
|
24 VDC positive logic transistor outputs
|
||
Nominal values
|
Voltage
|
24 VDC
|
|
Current
|
0.1 A
|
||
Threshold values (1)
|
Voltage (including ripple)
|
19..30 V (34 V possible for 1 hour every 24 hours))
|
|
Current/channel
|
0.125 A
|
||
Current/module
|
3.2 A
|
||
Power of tungsten filament lamp
|
Maximum
|
1.2 W
|
|
Leakage current
|
at 0
|
< 0.1 mA (for U = 30 V)
|
|
Voltage drop
|
at 1
|
< 1.5 V (for I = 0.1 A)
|
|
Load impedance
|
minimum
|
220 Ohms
|
|
Response time (2)
|
1.2 ms
|
||
Frequency of switching to inductive load
|
0.5 / LI2 Hz
|
||
Paralleling of outputs
|
Yes (maximum of 3)
|
||
Compatibility with IEC 1131-2 DC inputs
|
Yes (type 1 and type 2)
|
||
Built-in protection
|
against over-voltage
|
Yes, by Transil diode
|
|
against inversions
|
Yes, by inverted diode (3)
|
||
against short-circuits and overloads
|
Yes, by current limiter and electric circuit-breaker 0.125 A < Id < 0.185 A
|
||
Pre-actuator voltage check threshold
|
OK
|
> 18 V
|
|
Error
|
< 14 V
|
||
Check response time
|
on appearance
|
T < 4 ms
|
|
on disappearance
|
T < 30 ms
|
||
5 V consumption
|
typical
|
135 mA
|
|
maximum
|
155 mA
|
||
24 V pre-actuator consumption (4)
|
typical
|
30 mA
|
|
maximum
|
40 mA
|
||
Dissipated power (5)
|
1.6 W + (0.1 x Nb) W
|
||
Dielectric strength
|
Output / ground or Output / internal logic
|
1500 V actual, 50 / 60 Hz for 1 min
|
|
Insulation resistance
|
> 10 MOhms (below 500 VDC)
|
||
The characteristics at 60°C are guaranteed for 60 % of max. module current
|
|||
Legend:
|
|||
(1)
|
For U ≤ 30 V or 34 V.
|
||
(2)
|
All the outputs are equipped with fast electromagnet demagnetization circuits. Electromagnet discharge time < L/R
|
||
(3)
|
Fit a 2 A fuse to the +24 V pre-actuator supply (1 per connector).
|
||
(4)
|
Excluding load current.
|
||
(5)
|