The TSX DSY 08R5A module
|
5 A thermal current relay outputs
|
|||||
Direct
|
19..60 V
|
|||||
Alternating
|
19..264 V
|
|||||
Thermal current
|
5 A
|
|||||
Maximum current per common
|
6 A (value not to be exceeded)
|
|||||
Alternating current load
|
Resistive AC12
|
Voltage
|
24 V
|
48 V
|
100..120 V
|
200..240 V
|
Power
|
100 VA (5)
|
100 VA (6)
200 VA (4)
|
220 VA (6)
440 VA (4)
|
440 VA (6)
|
||
Inductive AC14 and AC15
|
Voltage
|
24 V
|
48 V
|
100..120 V
|
200..240 V
|
|
Power
|
50 VA (4)
|
20 VA (10)
50 VA (8)
|
20 VA (11)
110 VA (7)
220 VA (2)
|
20 VA (11)
110 VA (9)
220 VA (6)
440 VA (1)
|
||
Direct current load
|
Resistive DC12
|
Voltage
|
24 V
|
48 V
|
-
|
-
|
Power
|
24 W (6)
50 W (3)
|
50W (6)
100 W (3)
|
-
|
-
|
||
Inductive DC13 (L/R = 60 ms)
|
Voltage
|
24 V
|
48 V
|
-
|
-
|
|
Power
|
10 W (8)
24 W (6)
|
24 W (8)
50 W (6)
|
-
|
-
|
||
Response time
|
Activation
|
< 10 ms
|
||||
Deactivation
|
< 15 ms
|
|||||
Type of contact (12)
|
2 x 2 O/C
2 x 2 C
|
|||||
Built-in protection
|
against over-voltage
|
R-C and Ge-Mov circuit
|
||||
against short-circuits and overloads
|
6.3 A interchangeable quick-blow fuse per common
|
|||||
Dissipated power (13)
|
0.25 W + (0.24 x Nb) W
|
|||||
Dielectric strength
|
Output / ground or Output / internal logic
|
2000 V actual, 50 / 60 Hz for 1 min
|
||||
Insulation resistance
|
> 10 MOhms (below 500 VDC)
|
|||||
Power supply consumption
|
5 V
|
Typical
|
55 mA
|
|||
Maximum
|
65 mA
|
|||||
24 V relay (14)
|
Typical
|
10 mA
|
||||
Maximum
|
12 mA
|
|||||
Legend:
|
||||||
(1)
|
0.1 x 106 maneuvers
|
|||||
(2)
|
0.15 x 106 maneuvers
|
|||||
(3)
|
0.3 x 106 maneuvers
|
|||||
(4)
|
0.5 x 106 maneuvers
|
|||||
(5)
|
0.7 x 106 maneuvers
|
|||||
(6)
|
1 x 106 maneuvers
|
|||||
(7)
|
1.5 x 106 maneuvers
|
|||||
(8)
|
2 x 106 maneuvers
|
|||||
(9)
|
3 x 106 maneuvers
|
|||||
(10)
|
5 x 106 maneuvers
|
|||||
(11)
|
10 x 106 maneuvers
|
|||||
(12)
|
O = open (idle); C = closed (operation)
|
|||||
(13)
|
Nb = number of outputs at 1.
|
|||||
(14)
|
Per channel at 1.
|