Characteristics of the TSX DEY 16A5 module
(Original Document)
At a Glance
This section provides a description of the general characteristics of the TSX DEY 16A5 module.
General characteristics
The following table shows the general characteristics of the TSX DEY 16A5 module:
The TSX DEY 16A5 module
200..240 VAC alternating voltage inputs
Nominal input values
Voltage
200..240 VAC
Current
15 mA
Frequency
50 / 60 Hz
Threshold input values
at 1
Voltage
≥ 159 V
Current
≥ 6 mA (for U = 159 V)
at 0
Voltage
≤ 40 V
Current
≤ 4 mA
Frequency
47..63 HZ
Sensor supply
170..264 V
Peak current at activation (at nominal U)
300 mA
Input impedance
at nominal U
20 kOhms
Response time
Activation
10 ms
Deactivation
20 ms
IEC 1131-2 compliance
type 1
IEC 947-5-2
Dielectric strength
Input / ground or Input / internal logic
2000 V actual, 50 / 60 Hz for 1 min
Insulation resistance
> 10 MOhms (below 500 VDC)
Type of input
Capacitive
Sensor voltage check threshold
OK
> 164 V
Error
< 80 V
Check response time
on appearance
20 ms < T < 50 ms
on disappearance
5 ms < T < 15 ms
5 V consumption
typical
80 mA
maximum
90 mA
Sensor supply consumption (1)
typical
12 mA + (12 x Nb) mA
maximum
16 mA + (12 x Nb) mA
Dissipated power (1)
1 W + (0.4 x Nb) W
The characteristics at 60 °C are guaranteed for 60 % of inputs set to 1
Legend:
(1)
Nb = number of channels at 1.