Characteristics of the alternating voltage TSX DEY 16A2 module
(Original Document)
At a Glance
This section provides a description of the characteristics of the alternating voltage TSX  DEY 16A2 module.
Characteristics
The following table shows the characteristics of the alternating voltage TSX DEY 16A2 module:
The TSX DEY 16A2 module
24 VAC alternating voltage inputs
Nominal input values
Voltage
24 VAC
Current
15 mA
Frequency
50 / 60 Hz
Threshold input values
at 1
Voltage
≥ 10 V
Current
≥ 6 mA (for U = 10 V)
at 0
Voltage
≤ 5 V
Current
≤ 4 mA
Frequency
47..63 HZ
Sensor supply
20..26 V
Peak current at activation (at nominal U)
15 mA
Input impedance
at nominal U
1.6 kOhms
Response time
Activation
15 ms
Deactivation
20 ms
IEC 1131-2 compliance
type 2
IEC 947-5-2
Dielectric strength
Input / ground or Input / internal logic
1500 V actual, 50 / 60 Hz for 1 min
Insulation resistance
> 10 MOhms (below 500 VDC)
Type of input
Resistive
Sensor voltage check threshold
OK
> 18 V
Error
< 14 V
Check response time
on appearance
20 ms < T < 50 ms
on disappearance
5 ms < T < 15 ms
5 V consumption
typical
80 mA
maximum
90 mA
Sensor supply consumption (1)
typical
15 mA + (15 x Nb) mA
maximum
19 mA + (15 x Nb) mA
Dissipated power (1)
1 W + (0.35 x Nb) W
The characteristics at 60 °C are guaranteed for 60 % of inputs set to 1
Legend:
(1)
Nb = number of channels at 1.