The TSX DEY 16D2 module
|
24 VDC positive logic inputs
|
||
Nominal input values
|
Supply
|
24 VDC
|
|
Current
|
7 mA
|
||
Threshold input values
|
at 1
|
Supply
|
≥ 11 V
|
Current
|
≥ 6.5 mA (for U = 11 V)
|
||
at 0
|
Supply
|
≤ 5 V
|
|
Current
|
≤ 2 mA
|
||
Sensor supply (including ripple)
|
19..30 V (possibly up to 34 V, limited to 1 hour every 24 hours)
|
||
Input impedance
|
at nominal U
|
4 kOhms
|
|
Response time
|
minimum
|
4 ms
|
|
maximum
|
7 ms
|
||
IEC 1131-2 compliance
|
type 2
|
||
IEC 947-5-2
|
|||
Dielectric strength
|
1500 V actual, 50 / 60 Hz for 1 min
|
||
Insulation resistance
|
10 MOhms (below 500 VDC)
|
||
Type of input
|
current sink
|
||
Paralleling of inputs (1)
|
yes
|
||
Sensor voltage check threshold
|
OK
|
> 18 V
|
|
Error
|
< 14 V
|
||
Check response time
|
on appearance
|
1 ms < T < 3 ms
|
|
on disappearance
|
8 ms < T < 30 ms
|
||
5 V consumption
|
typical
|
80 mA
|
|
maximum
|
90 mA
|
||
Sensor supply consumption (2)
|
typical
|
25 mA + (7 x Nb) mA
|
|
maximum
|
33 mA + (7 x Nb) mA
|
||
Dissipated power (2)
|
1 W + (0.15 x Nb) W
|
||
The characteristics at 60 °C are guaranteed for 60 % of inputs set to 1
|
|||
Legend:
|
|||
(1)
|
This characteristic is used to connect several inputs to the same module in parallel, or to different modules for input redundancy.
|
||
(2)
|
Nb = number of channels at 1.
|