Characteristics of non removable static relay input adaptation bases ABE-7S16E2B1/E2E1/E2E0/E2F0/E2M0
|
|
(Original Document)
|
Base types
|
ABE-7S16E2B1
|
ABE-7S16E2E1
|
ABE-7S16E2E0
|
ABE-7S16E2F0
|
ABE-7S16E2M0
|
||
---|---|---|---|---|---|---|---|
Channel number
|
16
|
||||||
Command circuit characteristics (1)
|
|||||||
Nominal values
|
Voltage
|
24 VDC
|
48 VDC
|
48 VAC
|
110..130 VAC
|
230..240 VAC
|
|
Current
|
12 mA
|
13 mA
|
12 mA
|
8.3 mA
|
8 mA
|
||
Speed
|
-
|
-
|
50/60 Hz
|
||||
Input threshold
|
In state 1
|
Voltage
|
>= 13.7 V
|
>= 30 V
|
>= 32 V
|
>= 79 V
|
>= 164 V
|
Current
|
>= 5 mA
|
>= 6 mA
|
>= 5 mA
|
>= 4.5 mA
|
|||
In state 0
|
Voltage
|
<= 5 V
|
<= 10 V
|
<= 30 V
|
<= 40 V
|
||
Current
|
<= 2 mA
|
<= 1.5 mA
|
<= 2 mA
|
||||
Speed
|
-
|
-
|
47/63 Hz
|
||||
Sensor supply (ripple included)
|
19..30 V
|
38,4..60 V
|
38,4..53 V
|
96..143 V
|
184..264 V
|
||
Compliance with IEC 1131-2
|
type 1
|
type 2
|
type 1
|
||||
Response time
|
State 0 to 1
|
0.05 ms
|
20 ms
|
||||
State 1 to 0
|
0.4ms
|
20 ms
|
|||||
Maximum switching speed
|
1000 Hz
|
25 Hz
|
|||||
Voltage assigned to insulation
|
Input/output
|
300 V
|
|||||
Voltage assigned to shock resistance (1.2/50)
|
Input/output
|
2.5 kV
|
|||||
Key
|
|||||||
(1)
|
Operating piece inputs.
|