Base types
|
ABE-7R08S210
|
ABE-7R16S210
|
||
---|---|---|---|---|
Channel number
|
8
|
16
|
||
Contact characteristics
|
||||
Job limit voltage
|
Alternating
|
250 V
|
||
Direct
|
125 V
|
|||
Thermal current
|
5 A
|
|||
Alternating current load
|
Resistive, load AC12
|
Voltage
|
230 VAC
|
|
Current (1)
|
1,5 A
|
|||
Inductive, load AC15
|
Voltage
|
230 VAC
|
||
Current (1)
|
0.9 A
|
|||
Direct current load
|
Resistive, load DC12
|
Voltage
|
24 VDC
|
|
Current (1)
|
1.5 A
|
|||
Inductive, load DC13 (2)
|
Voltage
|
24 VDC
|
||
Current (1)
|
0.6 A
|
|||
Minimum switching
|
Current
|
10 mA
|
||
Voltage
|
5 V
|
|||
Response time
|
State 0 to 1
|
10 ms
|
||
State 1 to 0
|
5 ms
|
|||
Maximum speed of function loading
|
0.5 Hz
|
|||
Built-in protection measures
|
Against overloads and short-circuits:
|
None, provide one rapid fusion fuse per channel or group of channels.
|
||
Against alternating current inductive overcharging
|
None, each RC circuit or MOV (ZNO) suppressor, must be mounted on the posts of each pre-actuator appropriate to the voltage.
|
|||
Against direct current inductive overcharging
|
None, each discharge diode must be mounted on the posts of each pre-actuator.
|
|||
Voltage assigned to insulation
|
Coil/contact
|
300 V
|
||
Voltage assigned to shock resistance (1.2/50)
|
Coil/contact
|
2.5 kV
|
||
Key
|
||||
(1)
|
For 0.5 x 106 maneuvers.
|
|||
(2)
|
L/R = 10 ms.
|