The TSX PAY 262 modules provide the following functions:            
- 
Monitoring of emergency stop buttons and moving cover position switches for immediate halt (category 0 emergency stop in compliance with EN ISO 13850)             
- 
Channel de-synchronization detection (> 400 ms) in automatic start-up mode             
- 
Cabled safety block independent of Premium PLC operating mode             
- 
Guaranteed safety functions, whatever the safety system component failure, via:             
- 
Wiring of a (+) channel of an input x and of the (-) channel to another input (x+12) with a double contact             
- 
Self-checking and redundant design similar to the PREVENTA XPS-ASF range (cf. component catalog for Telemecanique safety applications)             
- 
Restart control via auxiliary input action: reactivation input             
- 
Possibility of monitoring the reactivation input by action on falling edge             
- 
Start-up mode selection using external cabling: manual, automatic or on falling edge             
- 
Automatic output check by monitoring their status reading in the feedback loop             
- 
Automatic input channel check by constant comparison of their respective statuses             
- 
Full safety system diagnostics via:             
- 
monitoring the SS ESD or PS input status readings             
- 
monitoring the reactivation input reading             
- 
monitoring the feedback loop reading             
- 
monitoring the safety output control reading            
- 
monitoring the safety system power supply status reading            
- 
monitoring the external module supply            
 
- 
Possibility to choose whether external supply is monitored or not